background image

Instructions for 

Digitrip RMS 500 Trip Unit 

Table of  Contents 

1 .0 

General  Description . . . . . . . . . . . . . . . . . . . . . . . . .  . 

1 . 1  

Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

1 .2 

Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

1 .3 

Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

2.0 

UL Listed  Devices . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

3.0 

Principle of  Operation . . . . . . . . . . . . . . . . . . . . . . .  . 

3.1 

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

3.2 

Trip and Operation  Indicators . . . . . . . . . . . . . . . .  . 

3.3 

Test Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

3.4 

Making Cu rrent  Release  (Discrimi nator)  . . . . . .  . 

3.5 

Instantaneous Override  . . . . . . . . . . . . . . . . . . . . .  . 

3.6 

Zone Interlocki ng  . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.0 

Protection  Settings . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.1 

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.2 

Long  Delay Settings  . . . . . . . . . . . . . . . . . . . . . . . .  . 

4.3 

Long  Delay Time Setti ngs . . . . . . . . . . . . . . . . . . .  . 

4.4 

Short  Delay Pick-up Settings  . . . . . . . . . . . . . . . .  . 

4.5 

Short Delay Time Settings  . . . . . . . . . . . . . . . . . .  . 

4.6 

Instantaneous  Pick-up Settings  . . . . . . . . . . . . . .  . 

4.7 

G round  Fault Cu rrent Pick-up Setti ngs  . . . . . . .  . 

4.8 

G round  Fault Time Delay Settings  . . . . . . . . . . .  . 

5.0 

Integral Test Panel - Test Procedu re  . . . . . . . . .  . 

5.1 

General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.2 

When To Test  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.3 

Test Provision  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.4 

Mode of Conducting Tests  . . . . . . . . . . . . . . . . . .  . 

5.4.1 

Control  Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

5.4.2 

By  Not Tripping  the  Breaker . . . . . . . . . . . . . . . . .  . 

5.4.3 

By Tri pping the  Breaker . . . . . . . . . . . . . . . . . . . . .  . 

6.0 

Back-up Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  

6.1 

General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

6.2 

Battery Check  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

6.3 

Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . .  . 

7.0 

Auxiliary Power Module . . . . . . . . . . . . . . . . . . . . .  . 

8.0 

Rati ng  Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

9.0 

References  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

9.1 

Type  DS  Low Voltage AC Power Circuit 

Breakers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

9.2 

Type  SPB Systems  Pow-R  Breakers . . . . . . . . . .  . 

9.3 

Dig itrip  RMS Trip Assem bl ies  . . . . . . . . . . . . . . .  . 

9.4 

Series C®  R-Frame  Molded Case Circuit 

Breakers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  . 

WARNING 

DO NOT ATTEMPT TO I N STALL OR PERFORM MAIN­
TENANCE ON EQU IPMENT WHILE IT IS E N E RGIZED. 
DEATH OR SEVERE PERSONAL INJ U RY CAN RESULT 
FROM  CONTACT  WITH  E N ERG IZED  EQUIPME NT. 

ALWAYS  VER I FY  THAT  NO  VOLTAGE  IS  PRESENT 

B E F O R E   P R O C E E D I N G   W I T H   T H E   TAS K ,   A N D  

ALWAYS  FOLLOW G E N ERALLY ACCEPTED SAFETY 

P R OC E D U R E S .   T H E   WESTI N G H O U S E   ELECTR I C  
CORPORATION  IS N OT  LIABLE F O R  T H E  MISAPPLI­
CATION OR MISINSTALLATION OF ITS  PRODUCTS. 

Page 


























1 0  
1 0  
1 0  
1 0  
1 0  
1 0  
1 1  

1 1  
1 1  
1 1  

1 1  

The user is cautioned to observe all recommendations, warn­
i ngs and cautions relating to the safety of personnel and equip­

ment, as wel l  as all general  and  local  health  and safety  laws, 
codes,  and  procedures. 

The  recommendations  and  i nformation  contained  herein  are 

based on Westi ng house experience and judgement, but should 

Effective  May, 1 989 Supersedes I . L.  29-851  dated  March,  1 988 

I.L.  29-851-A 

not be considered to  be a l l -incl usive  or covering every  appli­
cation or circumstance which may a rise. lf,any questions arise, 
contact  Westinghouse  Electric  Corporation  for  further  infor­
mation or instructions. 

1 .0  General  Description 

1 . 1   Protection 

The  Digitrip R M S  500 Trip U n it, illustrated  in  Fig. 1 ,  is a micro­

processor based type trip suitable for use in type SPB Systems 
Pow-R circuit breakers and types  DS and DSL  low voltage AC 

power  circuit  breakers  and  Series  C®  R-Frame  molded  case 
circuit breakers. 

The  trip  u n'it  provides  true  RMS  current  sensing  for  proper 
correlation  with  thermal  characteristics  of  conductors  and 

equi pment. I nterchangeable rating p l ugs are provided to estab­
lish the contin uous current  rating  of each  circuit  breaker. 

The  Digitrip  RMS  500 Trip  U n it  is  completely  self-contained 

and  when  the  circuit  breaker  i s  closed,  requ i res  no  external 

control  power to  operate  its 

protection  systems. 

It  operates 

from  current signal  levels and control  power derived through 
current sensors i ntegrally mounted  in the circuit breaker. 

The  Digitrip  RMS 500 Trip U nit is available in six optional pro­
tection  models.  Each trip  unit  may  be  equi pped with  a  maxi­

mum of five phase and two g round (time-current) adjustments 

to  meet  specific  application  requ i rements.  These  protection 

models  include  the  fol lowi ng  types  which  are  further  i l l us­

trated  in the  nameplate examples  shown  in  Fig.  2. 

Figure 

Type  Protection 

2 . 1  

Long Time/Instantaneous 

2.2 

Long Time/Short Ti me 

2.3 

Long Time/Short Time/Instantaneous 

2.4 

Long Time/Instantaneous/G round 

2.5 

Long Time/Short Time/Ground 

2.6 

Long Time/Short Time/I nstantaneous/ 
G round 

1 .2 

Information 

Identifier 

(LI) 
(LS) 
(LSI) 
(LIG) 
( LSG) 
(LSI G) 

Red LED indicators are provided on the face of the trip unit 

to  indicate the mode of  an  automatic trip operation. A  bat­
tery is provided to maintain the  mode  of  trip  LED indication 
fol lowing an automatic trip operation. 

Green LEOs are provided to indicate the operational status of 

the  trip u nit and the status of the  back-up battery  mounted  i n  

the  rating  plug. 

1 .3  Testing 

An  integral test panel, i ncluding a test selector switch  and test 
and  reset  pushbuttons,  is  provided to  test  the  circuit breaker 

in  either  a  "Tri p"  or  " No-Trip"  test  mode  under  qual ified 

conditions. 

2.0  UL  Listed  Devices 

Digitrip  R M S   500  Trip  U nits  are  l i sted  by  the  U n derwriters 
Laboratories,  I nc.  for  use  in  types  SPB,  DS  and  DSL  and 
Series C  R-Frame circuit breakers u nder U L  File E78 1 9. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Digitrip RMS 500

Page 1: ...act Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 5 00Trip Unit illustrated in Fig 1 is a micro processor based typ...

Page 2: ...ade m U S A VJ N Lithium Battery Only Long Delay Long Delay Setting Time In IT Sec At 61n 0 0 Breaker Trips In 6 T Test Amps IIJ in 0 Test 0 b Trip o IT In Reset 0 t n us lnst NP156P656H01 Fig 2 1 Lon...

Page 3: ...P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse Digital Protection D1g1tr1p RMS 500 CeliNa ___ 1NP256P655HOI Made 1n U S A II N L1th1um Battery Only Long Delay LongDelay Set...

Page 4: ...e pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashion to initiate prote...

Page 5: ...with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a specific value t...

Page 6: ...er in which the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit bre...

Page 7: ...me _____ I I I I I r Q Sec S 1 1 I I I u M I 1 1 I I I _ j 1 1 f l I I _ Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response I I I m 1 j 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response...

Page 8: ...t all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this value will b...

Page 9: ...g 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection functio...

Page 10: ...INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliary...

Page 11: ...ype SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master...

Page 12: ...Westinghouse Electric Corporation Distribution and Control Busi ness Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Page 13: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Page 14: ...0 l Cell No NP156P655H01 Made tn U S A y N Lith1um Battery Only Long Delay Long Delay Setting Time QJ In IT sec At 61n 0 0 Breaker Trips In 6T Test Amps ill In 0 Test 0 Trip 0 I In Reset 0 us lnst NP1...

Page 15: ...Amps 0 In 0 Test 0 Tnp 0 Reset Unit Status NP156P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1g1tal Protection Digitnp RMS 500 Cell No Gnd Fault Pickup In 0 long Delay...

Page 16: ...dly compared with the pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashi...

Page 17: ...not equipped with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a spec...

Page 18: ...the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Spe ci...

Page 19: ...I I Short Delay Time I 1 I I I Sec 0 1 1 I I I u I 1 1 I I I 1 1 1 In Viewing Window Indicates l t Type Response I I l J I I w Fig 4 4 Short Delay Time Settings r 1 I I I I lnst I I In i_ J 0 Availabl...

Page 20: ...e trip unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this va...

Page 21: ...Fig 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection func...

Page 22: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Page 23: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Page 24: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Page 25: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Page 26: ...No I NP256P655H01 Made in U S A lj3 N Lithium Battery Only Long Delay Long Delay Setting T1me ITJ in I Sec At 61n 0 0 Breaker Trips In 6T Test Amps In 0 Test 0 0 Trtp 0 I In Reset 0 us lnst NP256P656H...

Page 27: ...lay Time 0 Sec 0 b Ovemde D1scnmlnator Test 0 Trip o Reset NP256P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1gital Protection Digitnp RMS 500 Cell No r NP256P655H01 Mad...

Page 28: ...hich the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Sp...

Page 29: ...I I I I I Sec 0 I I I I I u _ M I I t 1 I I I 1 t 1 I I Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response r j I I ill 1 J 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response l t Respons...

Page 30: ...unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating Onl Any attempt to conduct in service testing above this value wi...

Page 31: ...6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fau lt condition occur during an in service No Trip Test sequence the protection function...

Page 32: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Page 33: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Page 34: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Reviews: