3.3 Test Provisions
An i ntegral test panel, i ncluding a test selector switch and test
and reset pushbuttons, is provided to test the circuit breaker
i n either a TRIP or NO-TRI P test mode u nder qualified condi
tions. See Section 5.
For bench testing of the trip unit alone or of the trip unit whi l e
it is insta l led i n t h e circuit breaker, a n optional Auxi l iary Power
Module (Cat. No. PRTAAPM) as shown in Fig. 7 is available.
This Auxiliary Power Module, which operates from a separate
1 20 Vac supply, may also be used when a drawout type circuit
breaker is i n any of its fou r cell positions, i .e., "Connected",
"Test", "Disconnected" and "Withdrawn" (or "Removed.")
3.4 Making Current Release (Discriminator)
When the DIGITRIP RMS 500 Trip Unit is not equipped with an
adjustable i n stantaneous protection setti ng, i .e., types LS or
LSG, a making current release (or d i scrim inator) circuit is pro
vided. This circu it wi l l prevent the circuit breaker from being
closed and latched-in on a faulted circu it. The non-adjustable
release is pre-set at eleven ( 1 1 ) times the i n stalled rating plug
a mpere rating On l·
The making current release is a rmed only for the first ten ( 1 0)
cycles fol lowing an i n itial ci rcuit breaker closing operation with
a load current exceeding approximately 20% ofthe circuit breaker
frame or sensor rati ng. Should the load cu rrent through the
circuit breaker drop to a value less than this, the release will
re-arm. The release, once armed, will remain armed u ntil the
load current passing through the circuit breaker exceeds
approximately 20% for 1 0 cycles. Any trip operation i nitiated
by the making current release will trip the circuit breaker
i n stantaneously.
5
3.5 Instantaneous Override
In addition, when the Digitrip RMS 500 Trip Unit is not equipped
with a n adjustable i n stantaneous setting, i.e., types LS o r LSG,
a high-set non-adjustable instantaneous override trip circuit is
provided. This h i g h level tripping action is pre-set to a specific
value that reflects the short time withstand rating of the circuit
breaker i n which the trip unit is i n stalled. Specific values vary
between ci rcuit breaker types and ratings. For specific i nfor
mation, refer to the supplementary leaflets and/or time-current
curves referenced in Sections 9 . 1 and 9.2.
3.6 Zone Interlocking
As indicated in the block diagram in Fig. 3, zone interlock sig
nals are provided. For Digitrip R M S 500 Trip U n its equ i pped
with either ground fau lt or short time protection functions or
both, separate zone i nterlocking circuits are provided. When
util ized, these i nput/output signals must be connected i n the
ulti mate equipment assembly in l i ne with detai l s provided with
the specific circuit breaker connection d iagrams supplied with
the circuit breaker and referenced in Sections 9.1 and 9.2. Sim
i larly, if the zone i nterlocking function is chosen not to be used,
defeater connections on each circu it must be added as i l lus
trated in the same referenced diag rams.
4.0 Protection Settings
4.1 General
Prior to placing any circu it breaker in operation, a l l ava i lable
protection settings shou l d be set using values as recom
mended by the specifying eng ineer responsible for the i n stal
lation. The n u m ber of settings that must be made wi l l be a
- -
-
- - -
-
- - - - - -
-
- -
-
-
-
- - - - - - ---,
Typical Cause of Trip LEOs
Located on Front Panel
Multiplexer
(MUX)
Unit
Operating Status
Indicator
Integral
Test
Panel
Input
0
Protection
Funct1on
Switch
Settings and
Pushbuttons
Central
Processor
Multiplexer
(MUX)
Data Bus
Unit
(CPU)
I
I
I
I
I
(FTST) or Direct Trip
Flux Transfer Shunt Trip
Actuator (DTAl
Analog
Trip
Circuit
Zone
Interlock
Circuitry
IN
OUT
www
. ElectricalPartManuals
. com