background image

1 0  

Trip 

Unit 

Plug 

Plug 

for 

120 

Vac 

Receptacle 

Fig.  7 

Auxiliary Power Module 

6.  Reset and reclose the circuit  breaker fol lowi ng  establ ished 

operati ng procedures. 

6.0  Back-up  Battery 

6.1  General 

As  indicated  in  Figs. 3 and 6,  a  back-up battery  is  provided to 

mai nta i n  the  mode of trip  LED indication  i n  the  Digitri p  RMS 
500 Trip U nit. The back-up battery is located i n  the rating plug 
along  with  a  battery  check  pushbutton  and  a  g reen  battery 
check  LED. 

6.2  Battery  Check 

The  battery  is  a  long  l ife,  lith i u m   photo  type  unit.  The  ready 
status of the battery can be checked at any time by depressing 

the battery check pushbutton  and observing the "On" condi­

tion of the battery check LED as shown in Fig. 6. 1 .  If the battery 

check LED does  not tu rn  "ON", replace the battery. 

6.3  Battery  Replacement 

Should the battery require replacement, it can be easily replaced 
from the front of the trip  u nit by l owering the hinged cover of 
the  rating  plug  as shown  in  Fig. 6.2.  The  battery  can then  be 
removed  by p u l l i ng  the  battery  tab  as shown  in  Fig. 6.3. 

Note: 

The  battery can  be  replaced  at  any time with 

the  circu it  breaker  in  service  without  affecting  the 

operation  of  the  circu it  breaker  and  its  protection 
fu nction. 

The replacement battery shou l d  be the same type or equ iva­

lent. Acceptable 3.0 volt lith i u m  batteries may be obtai ned from 

the following companies under their type designation indicated : 

Company 

Model 

Varta Batteries,  Inc. 

1 50  Clarbrook Road 

Elmsford,  N .Y.  1 0523 

Du racell 
South  B roadway 

Tangtown, N .Y.  1 059 1 

{914)  591-7000 

U n ion Carbide Corp. 
Battery Products  Div. 
Eveready 

39  Old  Ridgebury  Road 
Danbury, CT 0681 7-0001 
{203) 794-7548 

CR  1 /3N 

DL  1 13 N  

2L-76BP 

CAUTION 

CARE  SHOULD BE  EXERCISED WHEN REPLACI N G  A 
BATTERY TO  I NSURE THAT THE CORRECT  POLAR­
ITIES  ARE  OBSERVED.  POLARITY  MARKI NGS  ARE 
SHOWN ON THE RATI N G  PLUG WHEN THE H I N G E D  
COVER IS O P E N  A S  I N DI CATED I N  FIGS. 6.2 AND 6.3. 

7.0  Auxiliary  Power  Module 

The  Aux i l iary Power  Module  {Cat.  No.  PRTAAPM),  i l l u strated 

in  Fig. 7, is an encapsu lated power supply that requ i res a  1 20 

Vac i nput at either 50 or 60  Hz.  It provides an  output of 32 Vdc 
{nominal 40 Vdc open  circuit)  which  can  be used for testing a 
Digitrip R M S  500 Trip  Un it. 

When  d rawout  construction  is  provided,  any  circuit  breaker 
equipped with a Digitrip RMS 500 Trip U n it can be conveniently 

set and tested  while  the circu it  breaker  is out of  its  cel l  or i n  

its  cell  i n  the  " Disconnect"  o r  "Withdrawn"  positions  using 

the Aux i l i a ry  Power Module. 

The Aux i l iary Power Mod u le  is equipped with  a  unique  plug­

i n  con nector  suitable only for plugging  i nto  the  keyed  recep­

tacle  of  a  Digitrip  RMS  Trip  U n it.  This  prohi bits the  possible 

use of an incorrect, but simi lar, type power module. The loca­
tion  of the keyed  receptacle for the auxiliary  power module is 
shown  in  Fig.  1 .  

8.0  Rating  Plug 

The  rating  plugs,  as  i l l u strated  in  Figs.  1  and 6,  a re  used  to 
esta blish  the  contin uous  ampere  rating  of  the  related  circuit 
breaker. All pick-up settings of the protection functions of the 
trip unit, i .e., long delay, short delay, i n stantaneous and g round 

fau lt  are selected  as a  m u ltiple of the rating plug  rating  !ln l· 

Different types and ratings a re ava i lable to  match  the  desi red 
ampere  rating  and  type  of circuit  breaker  i nto  which the trip 
u nit is to be installed. Also, since the rati ng plugs are frequency 
sensitive,  specific types a re  avai lable for  50  or 60  Hz system 
appl ications. 

Complete catalog descriptions of all available rating plugs a re 
given  i n  the  applicable circuit breaker supplementary i n struc­

tion leaflets. References to these documents a re given i n  Sec­
tions 9.1  and 9.2. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for Digitrip RMS 500

Page 1: ...act Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 5 00Trip Unit illustrated in Fig 1 is a micro processor based typ...

Page 2: ...ade m U S A VJ N Lithium Battery Only Long Delay Long Delay Setting Time In IT Sec At 61n 0 0 Breaker Trips In 6 T Test Amps IIJ in 0 Test 0 b Trip o IT In Reset 0 t n us lnst NP156P656H01 Fig 2 1 Lon...

Page 3: ...P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse Digital Protection D1g1tr1p RMS 500 CeliNa ___ 1NP256P655HOI Made 1n U S A II N L1th1um Battery Only Long Delay LongDelay Set...

Page 4: ...e pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashion to initiate prote...

Page 5: ...with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a specific value t...

Page 6: ...er in which the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit bre...

Page 7: ...me _____ I I I I I r Q Sec S 1 1 I I I u M I 1 1 I I I _ j 1 1 f l I I _ Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response I I I m 1 j 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response...

Page 8: ...t all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this value will b...

Page 9: ...g 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection functio...

Page 10: ...INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliary...

Page 11: ...ype SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master...

Page 12: ...Westinghouse Electric Corporation Distribution and Control Busi ness Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Page 13: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Page 14: ...0 l Cell No NP156P655H01 Made tn U S A y N Lith1um Battery Only Long Delay Long Delay Setting Time QJ In IT sec At 61n 0 0 Breaker Trips In 6T Test Amps ill In 0 Test 0 Trip 0 I In Reset 0 us lnst NP1...

Page 15: ...Amps 0 In 0 Test 0 Tnp 0 Reset Unit Status NP156P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1g1tal Protection Digitnp RMS 500 Cell No Gnd Fault Pickup In 0 long Delay...

Page 16: ...dly compared with the pre set protection function pick up settings and other operating data stored in the ROM or Read Only Memory The microcomputer software program is then used in decision tree fashi...

Page 17: ...not equipped with an adjustable instantaneous setting i e types LS or LSG a high set non adjustable instantaneous override trip circuit is provided This high level tripping action is pre set to a spec...

Page 18: ...the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Spe ci...

Page 19: ...I I Short Delay Time I 1 I I I Sec 0 1 1 I I I u I 1 1 I I I 1 1 1 In Viewing Window Indicates l t Type Response I I l J I I w Fig 4 4 Short Delay Time Settings r 1 I I I I lnst I I In i_ J 0 Availabl...

Page 20: ...e trip unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating In Any attempt to conduct in service testing above this va...

Page 21: ...Fig 6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fault condition occur during an in service No Trip Test sequence the protection func...

Page 22: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Page 23: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Page 24: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Page 25: ...ntact Westinghouse Electric Corporation for further infor mation or instructions 1 0 General Description 1 1 Protection The Digitrip RMS 500 Trip Unit illustrated in Fig 1 is a micro processor based t...

Page 26: ...No I NP256P655H01 Made in U S A lj3 N Lithium Battery Only Long Delay Long Delay Setting T1me ITJ in I Sec At 61n 0 0 Breaker Trips In 6T Test Amps In 0 Test 0 0 Trtp 0 I In Reset 0 us lnst NP256P656H...

Page 27: ...lay Time 0 Sec 0 b Ovemde D1scnmlnator Test 0 Trip o Reset NP256P656H31 Fig 2 5 Long Time Short Time Protection LSG Nameplate Westinghouse D1gital Protection Digitnp RMS 500 Cell No r NP256P655H01 Mad...

Page 28: ...hich the trip unit is installed Specific information on these settings is given in the supplemental instruction leaflet referenced in Sec tions 9 1 and 9 2 that is supplied with the circuit breaker Sp...

Page 29: ...I I I I I Sec 0 I I I I I u _ M I I t 1 I I I 1 t 1 I I Available Settings 0 1 0 2 0 3 0 4 0 5 Seconds with Flat Response r j I I ill 1 J 1 1 I I w 3 0 1 0 3 0 5 Seconds with l t Response l t Respons...

Page 30: ...unit all in service testing under Trip or No Trip conditions must be done at load current values no greater than 40 of the plug rating Onl Any attempt to conduct in service testing above this value wi...

Page 31: ...6 2 View with Hinged Cover Open and Battery Installed Fig 6 Typical Rating Plug 9 Should an actual overload or fau lt condition occur during an in service No Trip Test sequence the protection function...

Page 32: ...O INSURE THAT THE CORRECT POLAR ITIES ARE OBSERVED POLARITY MARKINGS ARE SHOWN ON THE RATING PLUG WHEN THE HINGED COVER IS OPEN AS INDICATED IN FIGS 6 2 AND 6 3 7 0 Auxiliary Power Module The Auxiliar...

Page 33: ...pe SPB Systems Pow R Breaker Typical Time Current Characteristic Curve LS for Type SPB Systems Pow R Breaker Typical Time Current Characteristic Curve G for Type SPB Systems Pow R Breaker SPB Master C...

Page 34: ...2 Westinghouse Electric Corporation Distribution and Control Business Unit Electrical Components Division Pittsburgh PA 1 5220 Style No 661 5C96H01 w w w E l e c t r i c a l P a r t M a n u a l s c o...

Reviews: