CONFIGURATION: GALLONS PER MINUTE
The Well Bubbler is compatible with 4-20mA flow meters, and will record and display
real-time flow rate. Once the flow meter is correctly installed and wired to the Well
Bubbler, set the Gallons Per Minute to match the output of the flow meter itself.
This parameter must match the 4-20mA output scaling of the flow meter exactly. Enter
the sensor’s rating here, or set the value to zero to disable the feature.
Only one flow meter can be wired to a Well Bubbler. If both the pulse-type flow meter
scaling, and the 4-20mA flow meter scaling are defined as non-zero values, the flow
rate from only the pulse-type unit will be measured and reported.
If this 4-20mA sensor is configured, and at least 4.0mA is not detected by the Well
Bubbler, the unit will display an error, indicating that the sensor cannot be read.
Note that some 4-20mA sensors will produce slightly less than 4.0mA at rest (for
example, 3.95mA). This will result in an error, until the sensor output exceeds 4.0mA.