CONFIGURATION: MEASUREMENT PERIOD
The Measurement Period determines how often the Well Bubbler will measure the
well level, and auxiliary sensors (flow rate, discharge pressure and pump current).
The lower the measurement period, the more often the Well Bubbler will operate.
Typical values for 10-120 models are five or fifteen minutes; 10-300 models can
sample between thirty and sixty minutes, when using solar power only.
When powered from an external 24V supply, all models can sample at up to five
minutes. Note that a smaller measurement period results in increased wear on
the compressor.
Each Well Bubbler will automatically increase its measurement period if the battery
is below 12.2V; the unit will stop operating and hibernate at battery voltages below
12.0V, to preserve the battery.