Parameter
Setting range
Presetting
Set to
Hydraulic variation
1…59
1
[________]
Collect. temp. minimum
0°C…70°C
20°C
[________]
PS Speed minimum
10%…100%
40%
[________]
Collect2 temp. minimum
0°C…70°C
20°C
[________]
PS2 Speed minimum
10%…100%
40%
[________]
Throughput meter
0.01…10.0 l/Impulse
0.25 l/Impulse
[________]
Volume flow
0.1 l/m…500.0 l/m
1.5 l/m
[________]
Volume flow 2
0.1 l/m…500.0 l/m
1.5 l/m
[________]
Heat capacity
0.01 kJ/lK…10.0 kj/lK
3.73 kJ/lK
[________]
Frost protection
-50°C…+20°C
-20°C
[________]
PWT Speed Minimum
10…100%
30%
[________]
Tank Diff. ON
0 K…40 K
7K
[________]
Tank Diff. OFF
0 K…40 K
4 K
[________]
Tank Temp. Minimum
0°C…70°C
40°C
[________]
Tank Temp. Setpoint
0°C…70°C
55°C
[________]
Tank Temp. Maximum
20°C…95°C
95°C
[________]
Tank Control Diff.
0…40K
15K
[________]
Legionella Temp. Setpoint
0°C…70°C
0°C
[________]
Circ. Temp. Setpoint
0°C…70°C
0°C
[________]
Setpoint Temp. Load transfer
0°C…90°C
75°C
[________]
Switch over range Maximum
0…100%
50%
[________]
Difference switch over operation
0…40K
5K
[________]
DHW Loading ON
0°C…90°C
30°C
[________]
PWW Speed Minimum
10…100%
30%
[________]
Circ. Diff. ON
0 K…40 K
5 K
[________]
Calorifier Diff. ON
0 K…40 K
7 K
[________]
Calorifier Diff. OFF
0 K…40 K
4 K
[________]
Diff. Calorifier Minimum
0K…40K
15K
[________]
Calorifier Temp. Setpoint
0°C…70°C
70°C
[________]
Calorifer Temp. Maximum
20°C…90°C
90°C
[________]
Calorifier Control Diff.
0K…40K
15K
[________]
Tank load.Diff ON
0K…40K
5K
[________]
Tank load.Diff OFF
0K…40K
2K
[________]
Swim. pool Diff. ON
0 K… 40 K
7 K
[________]
Swim. pool Diff. OFF
0 K…40 K
4 K
[________]
Swim. pool Control Diff.
0K…40K
15K
[________]
Swim. pool Temp. Setpoint
0°C…40°C
30°C
[________]
Swim. pool Temp. Maximum
20°C…95°C
35°C
[________]
Swim. pool Temp. Protect
20°C…95°C
40°C
[________]
Priority Solar Loading
0…3
0
[________]
Return Diff. ON
0 K…40 K
5 K
[________]
Return Diff. OFF
0 K…40 K
2 K
[________]
Return Temp. Maximum
20°C…105°C
95°C
[________]
Commissioning log of adjustable parameters ‘Change settings’ (please complete)