![Weishaupt WRSol 1.0 Manual Download Page 41](http://html.mh-extra.com/html/weishaupt/wrsol-1-0/wrsol-1-0_manual_953375041.webp)
41
4
TPU
TKO
TKR*
VIZ*
PS
PZW*
WW
KW
TPO
TSO
VIZ*
MFA
eBus
TKO
PS
TKV*
TKR*
PPS
X1:
N
1
N
2
N
3
N
4
5
6
TSO
PZW*
PWL
TKV*
TPO
TPU
PPS
PWL*
X2:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Variation 61: Tank cascade for DHW and heating (energy storage tank WES) with retrieval function
• Energy yield calculation (optional;
➭
Ch. 7.10)
• Circulation function without sensor (optional;
➭
Ch.7.15)
The WRSol 2.0 determines the temperature differential
between the collector sensor (TKO) and the reference
sensor. If a collector flow sensor (TKV) is fitted this is
included in the control.
As soon as the temperature differential between TKO and
TPU is greater than the value set (
Calorifier Diff. On
),
the solar pump is switched on and the storage tank is
topped up until the switch off condition (
Calorifier
Diff. Off
) or the maximum calorifier temperature has
been reached.
WES function (
➭
Ch. 7.23).
Depending on the average pump speed and the minimum
calorifier temperature, the external heat exchanger can be
blocked via the potential free
Multi-funct. Output
(MFA).
The DHW function (
➭
Ch. 7.14) can also influence the MFA
output.
With the charge reversal pump calorifier-tank (PPS) the
energy stored is transferred from the calorifier depending on
the calorifier temperature (TPO) and the tank temperature
(TSO) (
➭
Ch. 7.18).
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
* optional
TPU
TKO
PS
WW
KW
TPO
TSO
MFA
eBus
TKO
PS
TKV*
THR
VRA
X1:
N
1
N
2
N
3
N
L
4
5
6
TSO
PPS
PWL
TKV*
TPO
TPU
PPS
PWL
THR
AB
B
A
M
VRA
X2:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Variation 62: Tank cascade for DHW and heating (energy storage tank WES) with retrieval function, heating
support via 3 way valve
The WRSol 2.0 determines the temperature differential
between the collector sensor (TKO) and the reference
sensor. If a collector flow sensor (TKV) is fitted this is
included in the control.
As soon as the temperature differential between TKO and
TPU is greater than the value set (
Calorifier Diff.
On
), the solar pump is switched on and the storage tank is
topped up until the switch off condition (
Calorifier
Diff. Off
) or the maximum calorifier temperature has
been reached.
WES function (
➭
Ch. 7.23).
Depending on the average pump speed and the minimum
calorifier temperature, the external heat exchanger can be
blocked via the potential free
Multi-funct. Output
(MFA).
The DHW function (
➭
Ch. 7.14) can also influence the
MFA output.
With the charge reversal pump calorifier-tank (PPS) the
energy stored is transferred from the calorifier
depending on the calorifier temperature (TPO) and the
tank temperature (TSO) (
➭
Ch. 7.18).
With the three way valve for return temperature increase
(VRA) the available energy from the calorifier can be
utilised depending on the calorifier temperature (TPO) and
the heating return sensor (THR).
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
* optional