6
Minimum collector temperature of the
second collector field which must be
achieved before the solar pump (PS2)
is switched on.
Variation: 22…34, 50, 74
Setting range:
0°C…70°C
Presetting:
20°C
Collect2
temp.
minimum
20.0°C
Switch differential for the load pump
PWL. If the tank temp. setpoint is
less than this value, the PWL pump
is started (
➭
Ch. 7.14).
This switch differential is also used for
the energy management with the MFA
output (
➭
Ch. 7.2).
Variation:
1, 2, 3, 17…19, 21…23, 32…34,
43…45, 50, 51, 53…59, 61, 62, 64
Setting range:
0...40K
Presetting:
5K
PWL
loading
diff.
5.0K
Lowest limit value of modulation range
of second solar pump.
Variation: 22…34, 50, 74
Setting range:
10%…100%
Presetting:
40%
(A minimum of 30% should be maintained, otherwise the
gravity breaks of the hydraulic assembly will close).
PS2
speed
minimum
40%
6.3 Change setting
Selection of the system procedure
required. Depending on variation the
relevant displays are generated.
Hydraulic variations (
➭
Ch. 4)
Variation: 1…84
Presetting: 1
Note:
If the variation is changed, all setting
parameters must be checked and adjusted if
necessary. The parameters in selection menu
Options
must be adjusted to site specific
requirements.
Hydraulic
variation
1
Minimum collector temperature
which must be achieved before the
solar pump is switched on.
Variation: 1…45, 50…84
Setting range
0°C…70°C
Presetting:
20°C
Collect.
temp.
minimum
20.0°C
Lowest limit value of modulation
range of solar pump.
Variation: 1…45, 50…84
Setting range
10%…100%
Presetting:
40%
(A minimum of 30% should be maintained, otherwise the
gravity breaks of the hydraulic assembly will close
PS
speed
minimum
40%
Use:
This selection menu is used to carry out site specific
settings (preferably by a heating engineer).
Note:
Only the settings stored for the hydraulic
variation selected are displayed in the menu.
Settings without function in the selected
variation are not shown.
Change
Setting
Hydraulic variation
.
.
.
.
.
.
Multi funct. output
esc