77
7
Functions
7
Setting
Passive protection
Active protection (cooling function)
to 1.
to 2.1
to 2.2
0
1
X
2
X
3
X
X
4
X
5
X
X
In addition to the basic function of the controller it is
possible to further protect the system against overheating
via a passive and or active protection function. In the basic
function (setting 0) the solar pump is switched off if the
“
Tank Temp. Maximum
” or “
Calorifier Temp.
Maximum
” is exceeded. The pump is also switched off if
the collector temperature exceeds 120°C. The pump
switches on again once the collector has cooled to 80°C.
1. Passive protection:
If the collector temperature increases to above 80°C
and if the tank or calorifier temperature is above
“...Temp. Maximum” the solar pump is operated at
100%. The tank or calorifier is now loaded up to a
max. of 95°C, independent of the setting “...Temp.
Maximum”. Switch off again occurs if the collector
temperature exceeds 120°C or the switch off condition
“...Diff. Off” has been achieved. Switch on occurs at
80°C collector temperature, or when the tank/calorifier
temperature drops to 92°C, without the collector
temperature exceeding 120°C.
2. Active protection:
The following two active protection functions are
possible:
2.1 Release cooling function as soon as the collector
protection temperature and the “Tank Temp.
Maximum” or “Calorifier Temp. Maximum” has
been reached.
2.2 Release cooling function as soon as the
“Tank Temp. Maximum” or “Calorifier Temp.
Maximum” has been reached.
Once the cooling function has been released, and if the
collector temperature falls 8K below the lower tank or
calorifier temperature, the solar pump is started and
the tank/calorifier is discharged. Discharge is stopped
as soon as the collector temperature drops to 4K
above the tank/calorifier temperature or if it drops 15 K
below the max. tank/calorifier temperature.
The setting 1, 3 or 5 must not be made in
conjunction with a tank or calorifier, who’s
permissible maximum temperature lies below
95°C. The setting is also not permitted, if the
DHW pipework has not been equipped with
scald protection.
7.1 Collector protection
DANGER
If the cooling function is not required, setting 0 or 1 should
be selected.
Note:
• On hydraulic variations with plate heat
exchanger both pumps are activated.
• On hydraulic variations with tank cascade
only the tank with the lowest priority emptied.
Variation: 1…45, 50…84