6.5.7 Set heating circuit type#1 ... 8
A heating circuit type must be set for each heating circuit.
Depending on the heating circuit type set the following will be carried out automati-
cally:
▪
defined reduction of the value range,
▪
Parameter preconfigured with factory settings.
Setting range
FBH-heat-up
Floor warming
FBH-heating
Underfloor heating
Radiator 60
Low temperature layout of radiators
Radiator 70
Normal layout of radiators
Convector
Convectors
Universal
All controller settings possible.
Settings heating cir-
cuit type
Parameter 316/317
Floor
warming
Underfloor
heating
Radiator
60 °C
Radiator
70 °C
Convector
heating
Universal
Normal sup set
(1
Parameter
114
/
121
(2
Factory
presetting
25°C
35°C
60°C
75°C
Setback supl
set
(1
Parameter
115
/
122
(2
Factory
presetting
16°C
20°C
35°C
40°C
45°C
Gradient
Parameter
116
/
123
(2
Range of
values
2.5 - 6
4 - 10
8 - 20
11 - 25
11 - 40
2.5 - 40
Factory
presetting
2.5
5
10
12.5
12.5
10
Supply max
Parameter
342
/
362
(3
Range of
values
Parameter
341
… 50 °C
Parameter
361
… 50 °C
Parameter
341
… 75 °C
Parameter
361
… 75 °C
Parameter
341
…
80 °C
Parameter
361
…
80 °C
Parameter
342
…
82 °C
Parameter
362
…
82 °C
Factory
presetting
30°C
40°C
65°C
75°C
On Opti
Parameter
383
(3
Factory
presetting
(actual val-
ue)
1:15
00:4
5
00:3
0
2:00
Pre-setting
HC#2
Factory
presetting
60
20
10
Off
Room thermostat
Parameter
388
/
389
(3
Factory
presetting
Day Off
1 K
(1
Parameter only available with heating circuit setting control type
Const sup
.
(2
User level.
(3
Heating engineer level.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
45-106