5.2.4 Wiring diagram WCM-EM as heating circuit controller
M
Y1
N PE
Y2
230V
PE
L N
MFA1
PE
L N
eBUS
+ –
eBUS
+ –
B1
1
M
B3
1
M
B6
1
M
1
M
H1
L
E
MM1
N PE
WCM-EM 2.1
Mains
230V 1/N/PE 50Hz
H1
L
PE
N
L
N PE
MM1
M
1~
M1
F11
16A
eBUS
B6
B1
0 1
F
E
D
C
B
A 9 8 7 6
5
4
3
2
PWM
Plug
Colour
Connection
Remarks
230 V
black
Supply voltage
230 V AC/50 Hz
–
H1
turquoise
Variable input 230 V AC
Signal input with variable function
MFA 1
purple
Heating circuit pump
max. 5 A* **
MM1
yellow
Mixer motor
max. 5 A* **
eBUS
light blue
eBUS connection
–
B1
green
External sensor
QAC 31 (NTC 600
Ω)
Weather compensation via separate exter-
nal sensor for zone control
B6
white
Supply sensor
NTC 5 k
Ω
Heating circuit with separately controlled
supply level via mixer
blue
PWM control
Modulation of heating circuit pump speed
control
* for electronic high efficiency pumps max 1.5 Ampere. Separate relay required for
greater power consumptions.
** Power consumption of outputs MFA 1 and MM1 in total maximal 5A.