6.5.10 Set function of variable input H1
The settings described below are in each case activated with closed contact!
Setting range extension module heating circuit
Standby
Heating operation is prevented.
Frost protection remains activated.
Normal
Constant heating operation, setback phase is preven-
ted.
Setback
Constant setback operation, normal heating phase is
prevented.
Setting range extension module DHW
Standby
No DHW operation, circulation pump off, Legionella
function remains activated.
HE interlock
Blocks the heat exchanger for DHW operation.
Circ pump
Manually activated operation of the circulation pump.
The circulation pump starts when the contact is closed.
Once the contact is reopened, the pump runs on for the
duration set in
P609
(pulse mode).
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Extension module #2
.
✓
Menu
Extension module #2
is displayed.
▶
Press function key
H1-Fct HC
and, where applicable,
H1-Fct DHW
.
✓
Parameter
H1-Fct HC
and, where applicable,
H1-Fct DHW
is displayed.
▶
Make selection using the dial knob and save with function key
OK
.
01
01
Heating circuit
Extension module #2
Extension module #2
Heating circuit #1
Heating circuit #2
End
End
-
+
H1-Fct HC
401
End
H1-Fct HC
Standby
Output test HC
Standby
Standard
OK
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
50-106