6.5.20 Set maximum pump speed
Parameter is only displayed if a PWM pump is connected
This parameter is used to set the upper operating point of the PWM pump (maximum
load).
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Setting #2
.
✓
Menu
Setting #2
is displayed.
▶
Press function key
max pump speed
.
✓
Parameter
max pump speed
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
02
Setting #2
Boil.MC boost
2.0K
Mixer parameter 8.0K
min pump speed
50%
End
-
+
min pump speed
427
End
Standard
OK
50%
20% - 100%
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
60-106
Summary of Contents for WCM-EM 2.1
Page 107: ...83277502 3 2012 10 La ...