6.5.32 Set adaption#1 ... 8
The adaption is used to automatically match the gradient to the building.
The parameter is only displayed, if P315 is set to External/Room.
Setting range
Off
Adaption inactive.
On
Adaption effective.
Gradient is being adjusted.
Prerequisite for an adaption:
▪
External temperature max. 8 °C,
▪
setback operation of min. 6 hours must be set,
▪
parameter
318
must be set to
External/Room
,
▪
automatic operation (heating program 1 … 3).
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Control behaviour
.
✓
Menu
Control behaviour
is displayed.
▶
Press function key
Adaption#1
.
✓
Parameter
Adaption#1
is displayed.
▶
Set
ON
using the dial knob and save with function key
OK
.
02
Control behaviour
Room ther#1
1K
Room ther#2
1K
Adaption#1
Off
End
-
+
Adaption#1
507
End
Standard
OK
Off
Off - On
Active adaption is displayed:
▪
in line 4 of the standard display by
A
,
▪
i Info mode by
Adaption
.
0
12
24
i
A
Mon 21.May 07
19:20
1
Room temp
20.0°C
Heating program 1
During the adaption:
▪
Do not manually correct the heating reference line
▪
Do not change room temperature setpoint
▪
Do not interrupt voltage supply
▪
Radiator thermostats must be open
▪
External heat sources must be switched off
Following completed adaption, the
A
in the standard display is faded out.
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
79-106