58
Function
Non-inverting pin
Inverting pin
Reference pin
RS–485 standard B
A
C
Modbus standard D1
D0
common
Weidmüller
D+
D–
C
The RS–485 cable used to wire this equipment must fulfill the following specifications:
• Shielded twisted pair with 1.5 or 2 pairs (preferably 1.5 pairs)
• Braid shield, not foil shield
•
120 Ω characteristic impedance
• Cross section of individual wires 0.2 mm
2
(AWG24) or larger
The following are two examples of proper RS–485 cable:
• Belden: 3106 A
• Lapp Cable Unitronic Bus LD 2×2×0.22 (part number 2170204)
Modbus terminology:
• The Transclinic is a
slave
and a
server
from the viewpoint of the Modbus standard.
• A Scada or the program running in a PLC/datalogger is a
client
from the viewpoint
of the Modbus standard.
• A RS–485–to–Ethernet converter or the hardware of a PLC/datalogger is a
master
from the viewpoint of the RS–485 standard.
Guidelines for RS–485 field wiring of this equipment when installed inside PV
combiner boxes:
• The RS–485 bus topology must be a daisy chain.
• Short stubs (< 2 meters) are allowed inside the combiner boxes.
• Even though the RS–485 standard allows up to 1200 meters bus length at low bit
rates (i.e. 9600 bps and 19200 bps), we recommend staying below 500 meters.
•
Each end of the bus requires a 120 Ω 10 % ½ W termination resistor between D+
and D– (see the RS-485 wiring diagram). One end of the bus will be the RS–485
master (which may or may not include an internal termination option) and the other
end will be inside the combiner box farthest away from the master (in terms of
RS–485 cable distance).
Summary of Contents for Transclinic 14i+
Page 2: ......
Page 74: ...74 2 2 1...
Page 75: ...75 2 2 ISO 7000 0434B X1 X4 X2...
Page 76: ...76 X1 X4 X1 X4 X2 15 2 3 Transclinic DC 2 PV Modbus RTU SCADA PLC RS485 0 P DC 0 PV...
Page 79: ...79 3 DIP 5 40 80 31 50 40 PV 1 kV...
Page 82: ...82 3 2 PV PV X1 X4 X2 2 X1 X4 PV PV X2 PV PV PV PCS DC PV IEC 60947 DC 21B PCS...
Page 83: ...83 PV Transclinic X1 X4 X2...
Page 86: ...86 PV PV X2 PV X2 2 1 PV X1 X4 3 3 X3 PV 0 0 Vdc 1 24 Vdc 2 X3 Transclinic 24 Vdc X3...
Page 87: ...87 X3 0 2 2 5 mm2 0 2 4 mm2 7 mm 0 4 0 5 Nm 0 6 3 5 mm Transclinic X3 EMC 3m...
Page 89: ...89 Transclinic 2 5 Adc DC DC X6 EMC 3m...
Page 100: ...100 5 OFF Transclinic OFF OFF 15 5 40 31 80 40 50 PV 2 1 X1 X4 X2 DIN RS 485...
Page 101: ...101...
Page 103: ...103 LVD 2006 95 EC EMC 2004 108 EC CE WEEE 012 19 EU WEEE...
Page 105: ...105...
Page 110: ......