50
Negative
copper
busbars
Negative PV
current
inputs
Positive PV
voltage
input
Terminal / connector
–
X1, X4
X2
Stranded wire cross section
(with ferrule)
–
2.5 – 10 mm
2
2.5 – 6 mm
2
Stranded wire cross section
(without ferrule)
10 – 35 mm
2
2.5 – 16 mm
2
2.5 – 16 mm
2
Stranded wire cross section
(Transclinic 8i+: 30A/input)
(Transclinic 14i+: 20A/input)
4 × 35 mm
2
PV1–F
6 mm
2
PV1–F
–
Stranded wire stripping length
–
12 mm
12 mm
Tightening torque
4.5 Nm
1.2 – 1.5 Nm 1.2 – 1.5 Nm
Required tool
torque
wrench with
10 mm
ISO hex head
torque
wrench with
1 × 5.5 mm
flat-blade
torque
wrench with
1 × 5.5 mm
flat-blade
External insulation required
double or
reinforced
double or
reinforced
double or
reinforced
Wiring of X1 and X4
Connect the negative polarity of the PV inputs to these two terminal blocks. It is
recommended to evenly distribute the total input current between the two terminal
blocks X1 and X4.
WARNING
All negative PV current inputs must belong to the same inverter’s MPPT.
Wiring of the two negative copper busbars
Summary of Contents for Transclinic 14i+
Page 2: ......
Page 74: ...74 2 2 1...
Page 75: ...75 2 2 ISO 7000 0434B X1 X4 X2...
Page 76: ...76 X1 X4 X1 X4 X2 15 2 3 Transclinic DC 2 PV Modbus RTU SCADA PLC RS485 0 P DC 0 PV...
Page 79: ...79 3 DIP 5 40 80 31 50 40 PV 1 kV...
Page 82: ...82 3 2 PV PV X1 X4 X2 2 X1 X4 PV PV X2 PV PV PV PCS DC PV IEC 60947 DC 21B PCS...
Page 83: ...83 PV Transclinic X1 X4 X2...
Page 86: ...86 PV PV X2 PV X2 2 1 PV X1 X4 3 3 X3 PV 0 0 Vdc 1 24 Vdc 2 X3 Transclinic 24 Vdc X3...
Page 87: ...87 X3 0 2 2 5 mm2 0 2 4 mm2 7 mm 0 4 0 5 Nm 0 6 3 5 mm Transclinic X3 EMC 3m...
Page 89: ...89 Transclinic 2 5 Adc DC DC X6 EMC 3m...
Page 100: ...100 5 OFF Transclinic OFF OFF 15 5 40 31 80 40 50 PV 2 1 X1 X4 X2 DIN RS 485...
Page 101: ...101...
Page 103: ...103 LVD 2006 95 EC EMC 2004 108 EC CE WEEE 012 19 EU WEEE...
Page 105: ...105...
Page 110: ......