Parameters Description
Crane | 53
P1050 – Time to Enable a new Command to Brake Release
Adjustable
0.10 to 650.00 s
Factory Setting:
0.20 s
Range:
Proprieties:
Access groups via HMI:
SPLC
Description:
This parameter defines a time after the command to brake closing has been executed via the digital output of
the CFW500, so that a new command to load hoisting or load lowering is accepted and thus the brake can be
released again thus preventing a new command to be generated without the brake being closed mechanically.
NOTE!
The value of the set time should be sufficient to ensure that a new command to load hoisting or load
lowering performs with the brake closed, but that does not generate a very large delay in the crane
vertical motion operation.
NOTE!
Refer to the section 2.4 in this application manual for more information on the connection diagram
and brake power supply.
Figure 3.3 – Logic block diagram for the mechanical brake control through the digital output DO1