Parameters Description
Crane | 32
Description:
This parameter has different functions according to the speed reference control configuration:
■
P1023 = 0, it defines the maximum speed reference value for the crane. In other words, this is the maximum
value that the “acceleration” command via digital input DI4 can provide.
■
P1023 = 1 or 7, the parameter does not have a specific function for the crane.
■
P1023 = 2, 3, 4 or 5, it defines the value of the 2nd speed reference for the crane.
■
P1023 = 6, it defines the maximum speed reference value for the crane. In other words, it is the maximum
speed reference value when the value read at the analog input is 10 V or 20 mA.
P1033 – Speed Reference 3
Adjustable
0.0 to 500.0 Hz
Factory Setting:
P1023 = 0: 0.0 Hz
Range:
P1023 = 1: 0.0 Hz
P1023 = 2: 0.0 Hz
P1023 = 3: 60.0 Hz
P1023 = 4: 40.0 Hz
P1023 = 5: 30.0 Hz
P1023 = 6: 0.0 Hz
P1023 = 7: 0.0 Hz
Proprieties:
Access groups via HMI:
SPLC
Description:
This parameter has different functions according to the speed reference control configuration:
■
P1023 = 0, 1, 2, 6 or 7, the parameter does not have a specific function for the crane.
■
P1023 = 3, 4 or 5, it defines the value of the 3rd speed reference for the crane.
P1034 – Speed Reference 4
Adjustable
0.0 to 500.0 Hz
Factory Setting:
P1023 = 0: 0.0 Hz
Range:
P1023 = 1: 0.0 Hz
P1023 = 2: 0.0 Hz
P1023 = 3: 0.0 Hz
P1023 = 4: 60.0 Hz
P1023 = 5: 45.0 Hz
P1023 = 6: 0.0 Hz
P1023 = 7: 0.0 Hz
Proprieties:
Access groups via HMI:
SPLC
Description:
This parameter has different functions according to the speed reference control configuration:
■
P1023 = 0, 1, 2, 3, 6 or 7, the parameter does not have a specific function for the crane.
■
P1023 = 4 or 5, it defines the value of the 4th speed reference for the crane.