Crane
Crane | 23
2.3.4 Speed Reference via Communication Networks
The control connections (analog inputs/outputs and digital inputs/outputs) that must be made to connector of
the CFW500-ENC plug-in module of the CFW500 frequency inverter, for Crane Vertical or Horizontal Motion
with speed reference through communication networks, are presented next.
Figure 2.5 – Signals on connector of the CFW500-ENC plug-in module for crane with speed reference via
communication networks
NOTE!
Refer to the CFW500 frequency inverter manual and the CFW500-ENC installation guide for further
details about connections.
Conector
Default Function for Crane via Communication Networks
1
DO1-RL-NO
U
pp
er
Ter
m
in
al
Relay digital output 1 (DO1): Brake Release
3
DO1-RL-C
5
DO3-RL-NO
Relay digital output 3 (DO3): No Fault
7
DO3-RL-C
9
DO4-RL-NO
Relay digital output 4 (DO4): Run
11
DO4–RL-C
13
GND
Reference 0 V
15
AO1
Analog output 1: Not Used
17
AI1
Analog input 1: Speed Reference
19
DO2
Transistor digital output 2 (DO2): Not Used
21
+24V
Power 24 Vdc (150mA)
23
+VE
Encoder Power Supply 12 V (S2.1 = OFF) or 5 V (S2.1 = ON)
2
DI1
Low
er
Ter
m
in
al
Digital input 1: Not Used
4
DI2
Digital input 2: Emergency Stop
6
DI3
Digital input 3: Not Used
8
DI4
Digital input 4: Not Used
10
DI5
Digital input 5 (NPN): Not Used
12
RS485 - A
RS485 (Terminal A)
14
RS485 - B
RS485 (Terminal B)
16
GND
Reference 0 V
18
A
Quadrature A input motor encoder
20
/A
Inverted Quadrature A input motor encoder
22
B
Quadrature B input motor encoder
24
/B
Inverted Quadrature B input motor encoder