CONNECTING A DEVICE TO THE DRIVE SCAN
Table 5.18:
Ethernet hardware accessory of the SSW900 compatible with the Modbus TCP protocol
Accessory
WEG item
Modbus TCP
clients
SSW900
firmware
Parameters
CMB-TCP-N
12966038
2
≥
V1.00
Table 5.19
Table 5.19:
Parameters related to the CMB-TCP-N
Parameter
Net ID
Description
Values range
C8.3.4
760
IP address configuration
0 = Parameters
1 = DHCP
C8.3.5
762
IP address
0.0.0.0 a 255.255.255.255
C8.3.6
761
CIDR (subnet mask)
0 = Reserved
1 = 128.0.0.0
2 = 192.0.0.0
3 = 224.0.0.0
4 = 240.0.0.0
5 = 248.0.0.0
6 = 252.0.0.0
7 = 254.0.0.0
8 = 255.0.0.0
9 = 255.128.0.0
10 = 255.192.0.0
11 = 255.224.0.0
12 = 255.240.0.0
13 = 255.248.0.0
14 = 255.252.0.0
15 = 255.254.0.0
16 = 255.255.0.0
17 = 255.255.128.0
18 = 255.255.192.0
19 = 255.255.224.0
20 = 255.255.240.0
21 = 255.255.248.0
22 = 255.255.252.0
23 = 255.255.254.0
24 = 255.255.255.0
25 = 255.255.255.128
26 = 255.255.255.192
27 = 255.255.255.224
28 = 255.255.255.240
29 = 255.255.255.248
30 = 255.255.255.252
31 = 255.255.255.254
C8.3.7
766
Gateway
0.0.0.0 a 255.255.255.255
C8.3.9.1
771
Timeout mode
0 = Inactive
1 = F131 fault
2 = A131 alarm
C8.3.9.2
772
Timeout error action
0 = Only indicates
1 = Ramp stop
2 = General disable
3 = Go to LOC
4 = Go to REM
C8.3.9.3
759
Modbus TCP timeout
0 a 999,9s
5.6.3
POSSIBLE FORMS OF CONNECTIONS
Figure 5.9
illustrates the possible ways to connect the SSW900 to the Drive Scan.
Low Voltage Devices | 5-21