background image

3

b. 

Wiring one RH-250 and one RH-253 single pole 

momentary switch for multi-way Manual-ON/OFF single 

load control.

IMPORTANT: 

The RH-250 must be installed in the wiring wall box that 

connects to the load.

•  Connect the green or non-insulated (copper) GROUND wire 

in each wiring box to the green terminal on each RH-250 and 

RH-253.

•  Connect the NEUTRAL wire from the circuit and from the 

lamp (LOAD) to the white wire on the RH-250.

•  Connect the power wire from the circuit box (HOT) to one 

terminal of the RH-253 single pole momentary wall switch 

and to the TRAVELER 1 wire.

•  Connect the TRAVELER 1 wire coming from the RH-253 

wiring box to the black wire of the RH-250.

•  Connect the lamp power (LOAD) to the red wire on the  

RH-250.

•  Connect the TRAVELER 2 wire to the other side of the 

RH-253 single pole momentary wall switch and to the yellow 

wire of the RH-250.

5. 

Put all the new switches into their wall boxes.

Position the RH-250 switch(es) with the lens above the ON/OFF button 

(lens at top, ON/OFF button at bottom). Use the captive screws on the 

mounting strap to secure the switches to their wall boxes.

6. 

Restore power to the circuit.

Turn on the breaker or replace the fuse.

7. 

Make any necessary adjustments.

See the SENSOR ADJUSTMENT & PROGRAMMING section  

for information.

8. 

Install cover plates.

Install industry standard decorator wall switch cover plate (not 

included)

Initial Power-up

There is an initial warm-up period. If the sensor is in Mode 2 “Automatic 

ON” it may take up to a minute before the lights turn ON. However, 

the lights can be turned ON/OFF manually by pressing the “ON/OFF 

Button” at any time when power is supplied to the unit.

SENSOR ADJUSTMENT & PROGRAMMING

To program the RH-250, you use controls located under the ON/OFF 

button. The wall switch cover plate must be removed to gain access to 

the mode button and adjustment trimpots under the ON/OFF button.

1.  Firmly grasp the side edges of the Lock Bar and gently pull it 

away from the switch face until it clicks. Do NOT attempt to pull 

the Lock Bar off of the switch!

2.  Firmly grasp the side edges of the ON/OFF button. Slide the 

button downward approximately 1/2 inch to expose the mode 

button and adjustment trimpots.

For multi-way operation, the Operating Mode and the Time Delay 

adjustments should be the same in all sensors related to the same 

load. 

Setting up the Operating Mode

Select the operating mode by pressing the Mode button. The amber LED behind the switch button blinks to indicate the selected mode. The 

blink pattern repeats three times:

•  One blink indicates Mode 1 (Vacancy Sensor Operation), Manual-ON/OFF, Auto-OFF
•  Two blinks indicates Mode 2 (Occupancy Sensor Operation), Auto-ON/OFF with manual control and reset to auto (after 5 minutes of 

vacancy)

To change the mode, press the Mode button once to set the unit to mode 1 or press the Mode button twice to set the unit to mode 2. The LED 

blinks to indicate the selected mode. It repeats the selected mode three times. After that, the unit operates in the indicated mode.

Adjusting the Time Delay

Turn the right trimpot counter-clockwise to reduce the amount of time the lights will remain ON after the last motion detection (minimum = 15 

seconds). Turn the same trimpot clockwise to increase this time delay (maximum = 30 minutes). You can only select the following values: 15 

seconds/5 minutes/15 minutes/30 minutes.

Warning: Do not overturn the Time Delay adjustment trimpot!

RH-250

Red

Ground

Yellow

Black

White

Load

Traveler 2

Hot

Neutral

Traveler 1 (Hot)

TOP

INDOOR USE ONLY

RH-253

Ground

RH-253

Ground

Ground

Traveler 2

Traveler 1

Traveler 2

Traveler 1

Traveler 2

Traveler 1

120V/60Hz

AUXILIARY RH-250

MASTER RH-250

TOP

INDOOR USE ONLY

TOP

INDOOR USE ONLY

Red

Ground

Yellow

Black

White

Red

Ground

Yellow

Black

White

Load

Traveler 1

Traveler 2

Neutral

Hot

120V/60Hz

Neutral

Fig. 5 Step 4a. Reference wiring diagram

RH-250

 

TOP

INDO

OR U

SE O

NLY

L

L

Red – Load

(power to lamp 

or fan)

Ground

Terminal

White –

Neutral

Yellow – Traveler 2 

               to RH-253

Traveler 1

               to RH-250

Black-> Traveler 1

      power via RH-253

RH-253

Line (power from 

                      circuit box)

Traveler 2

   to RH-250

Ground

Terminal

Fig. 6: Step 4b. Sensor orientation and wire connections for 3-way 

operation with an RH-253 momentary wall switch

Fig. 7:  Step 4b. Reference wiring diagram for multi-way operation with 

RH-253 momentary wall switches (4 maximum)

To wire up to four RH-253 single pole momentary wall switches to one 

RH-250, wire them in parallel as shown in the following wiring diagram.

Summary of Contents for RH-250

Page 1: ...rolled load is OFF When the controlled load is ON the LED is OFF Operating Modes For multi way operation of two or more RH 250s we recommend that the Operating Mode be the same in all sensors related to the same load This makes it easier to understand the multi way control operation as well as trouble shooting There are two operating modes to select from MODE 1 Vacancy sensor Manual ON OFF Auto OF...

Page 2: ...ores to the length indicated by the Strip Gauge in Fig 3 approx 1 2 inch 4 Wire the sensor Twist the existing wires together with the wire leads on the RH 250 sensor s as indicated in either step 4a or 4b Cap wires securely using wire nuts a Wiring two RH 250s in a 3 way configuration Connect the green or non insulated copper GROUND wire from the circuit to the green terminal on each RH 250 Connec...

Page 3: ... 2 inch to expose the mode button and adjustment trimpots For multi way operation the Operating Mode and the Time Delay adjustments should be the same in all sensors related to the same load Setting up the Operating Mode Select the operating mode by pressing the Mode button The amber LED behind the switch button blinks to indicate the selected mode The blink pattern repeats three times One blink i...

Page 4: ...ted the TEST mode The controlled load turns ON for 5 seconds each time the sensor detects motion After 5 seconds expire without motion detection the load turns OFF The controlled load turns ON automatically with the next motion detection and stays ON for 5 seconds 4 Repeat as necessary to ensure that the desired coverage areas are within detection range You can do this test for each RH 250 in your...

Page 5: ...inte manuellement l activation automatique est réactivée lorsqu aucun mouvement n est détecté pendant 5 minutes Cela permet d éviter que la charge ne s active automatiquement après avoir été volontairement désactivée Temporisation La temporisation peut être sélectionnée par l utilisateur pendant la configuration Elle peut être réglée sur l une des valeurs fixes suivantes 15 secondes 5 minutes 15 m...

Page 6: ...lage au fil blanc du RH 250 auxiliaire Raccordez le fil d alimentation de la boîte de circuits SOUS TENSION au fil noir du RS 250 auxiliaire et au fil VA ET VIENT 1 Raccordez le fil VA ET VIENT 1 depuis le fil noir du RH 250 auxiliaire au fil noir du RH 250 maître Raccordez le fil d alimentation de la lampe CHARGE au fil rouge du RH 250 maître Scellez le fil rouge sur le RH 250 auxiliaire Connecte...

Page 7: ... d inoccupation marche arrêt manuels extinction automatique Deux clignotements indiquent le mode 2 fonctionnement détecteur de présence marche arrêt automatique avec commande manuelle et réinitialisation à la commande automatique après 5 minutes d inoccupation Pour changer le mode appuyez une fois sur le bouton Mode pour régler l appareil au mode 1 ou appuyez deux fois sur le bouton Mode pour régl...

Page 8: ...tecteur repère un mouvement Après 5 secondes passées sans détection la charge s éteint La charge contrôlée s active automatiquement lors de la prochaine détection et reste active pendant 5 secondes 4 Répétez les étapes autant de fois que nécessaire de sorte que le champ de détection soit conforme à la zone de couverture recherchée Vous pouvez effectuer ce test pour chaque RH 250 de votre configura...

Page 9: ...be presionar el botón de ENCENDIDO APAGADO para encender la carga Uno o varios RH 250s controlando una misma carga la mantendrán encendida hasta que ninguno de ellos detecte movimiento por un periodo de tiempo denominado Retardo de Apagado configurable desde 15 segundos hasta 30 minutos Existe un periodo de 30 segundos inmediatamente después de que la carga se ha apagado automáticamente durante el...

Page 10: ...le blanco del otro RH 250 denominado como auxiliar El término maestro es utilizado acá únicamente para designar el sensor que esta conectado directamente a la carga controlada Conecte el cable de LINEA o FASE del circuito al cable negro del RH 250 auxiliar y al cable VIAJERO 1 Conecte el cable VIAJERO 1 proveniente del cable negro del RH 250 auxiliar al cable negro del RH 250 maestro Conecte el ca...

Page 11: ...deará una ó dos veces según sea Modo 1 ó Modo 2 El LED repetirá el patrón seleccionado tres veces Después de eso la unidad estará programada para operar en el modo seleccionado Ajuste del Retardo de Apagado Gire la perilla izquierda en dirección contraria a las manecillas del reloj para reducir el tiempo que permanecerá encendida la carga después de la última detección de movimiento valor mínimo 1...

Page 12: ...zca inmóvil La carga controlada se apagará después de 5 segundos si el sensor no detecta movimiento 3 Movilícese dentro del área de cobertura La carga controlada se encenderá por 5 minutos cada vez que el sensor detecte movimiento Después de transcurridos 5 segundos de no detección la carga se apagará La carga se encenderá automáticamente con la próxima detección y se mantendrá encendida por otros...

Reviews: