background image

2

Coverage Area

The RH-250 has a maximum coverage range of 180 degrees and a coverage area of 600 square feet (56 

square meters). The sensor must have a clear and unobstructed view of the coverage area. Objects blocking 

the sensor’s lens may prevent detection thereby causing the light to turn OFF even though someone is in the 

area.

NOTE: 

Windows, glass doors, and other transparent barriers will obstruct the sensor’s view and prevent 

detection.

INSTALLATION & WIRING

These instructions describe only the 3-way circuit applications. 

For information about other applications,  

consult technical support.

1. 

Prepare the switch box

After the power is turned OFF at the circuit breaker box, 

remove the existing wall plate and mounting screws. Pull 

the old switch out from the wall box.

2. 

Identify the type of circuit

You may connect the RH-250 to a single pole or multi-way 

circuit. If you are unable to clearly identify some or all of the 

wires mentioned in this manual, you should consult with a 

qualified electrician.
In a 3-way circuit (see Fig. 2), two traveler wires connect 

to both switches. Another wire provides power from the 

circuit box to one of the switches. A wire connects from one 

switch to the load. A ground wire may also be connected to 

a ground terminal on the old switches. A neutral wire should 

also be present in both wall boxes.

CAUTION 

For your safety: Connecting a proper ground to the sensor provides protection against electrical shock in the event of certain  

fault conditions. If a proper ground is not available, consult with a qualified electrician before continuing installation.

3. 

Prepare the Wires

Tag the wires currently connected to the existing switch so that they can be identified later. Disconnect the wires. 

Make sure the insulation is stripped off of the wires to expose their copper cores to the length indicated by the 

“Strip Gauge,” in Fig. 3. (approx. 1/2 inch).

4. 

Wire the sensor

Twist the existing wires together with the wire leads on the RH-250 sensor(s) as indicated in either step 4a or 4b. Cap wires securely using 

wire nuts.

a. 

Wiring two RH-250s in a 3-way configuration

•  Connect the green or non-insulated (copper) GROUND 

wire from the circuit to the green terminal on each RH-

250.

•  Connect the NEUTRAL wire from the circuit and from 

the lamp (LOAD) to the white wire on the 

master

 RH-

250. 

• 

The term “master” designates the RH-250 that 

connects to the load.

•  Connect the NEUTRAL wire from the circuit in the other 

wiring box to the white wire on the auxiliary RH-250.

•  Connect the power wire from the circuit box (HOT) 

to the black wire on the auxiliary RH-250 and to the 

TRAVELER 1 wire.

•  Connect the TRAVELER 1 wire from the black wire of the auxiliary RH-250 to the black wire of the master RH-250.
•  Connect the lamp power (LOAD) to the red wire on the master RH-250.
•  Cap the red wire on the auxiliary RH-250.
•  Connect the TRAVELER 2 wire coming from the yellow wire of another RH-250 to the yellow wire of the RH-250 that you are wiring.

P

P

Fig. 1: Sensor Coverage Area

Strip Gauge

1/2"

12.7mm

Fig. 3: Wire Stripping

NEUTRAL

GROUND

LOAD/Common

(power to lamp)

GROUND

          HOT/Common

Lamp/load

TRAVELER

TRAVELER

(power from circuit box)

NEUTRAL

MASTER SWITCH

AUXILIARY SWITCH

Fig. 2: Typical 3-Way Switch Wiring

MASTER RH-250

AUXILIARY RH-250

qOT

 

 

TOP

INDO

OR U

SE O

NLY

L

L

Red – Load

(power to lamp 

or fan)

White – 

  Neutral

Red – capped

Ground

Terminal

White – 

Neutral

Yellow – Traveler 2

to AUX RH-250

Yellow – Traveler 2

     to Master RH-250

Line (power 

   from circuit box)

Black – Traveler 1

     power to

     Master RH-250

Black – Traveler 1

      power from

      AUX RH-250

Ground

Terminal

Fig. 4: Step 4a. Sensor orientation, wire connections and wall box 

assembly

WARNING

DISCONNECT POWER TO THE WALL SWITCH BOX BY  

TURNING OFF THE CIRCUIT BREAKER OR REMOVING THE 

FUSE FOR THE CIRCUIT BEFORE INSTALLING THE RH-250, 

REPLACING LAMPS, OR DOING ANY ELECTRICAL WORK.

Summary of Contents for RH-250

Page 1: ...rolled load is OFF When the controlled load is ON the LED is OFF Operating Modes For multi way operation of two or more RH 250s we recommend that the Operating Mode be the same in all sensors related to the same load This makes it easier to understand the multi way control operation as well as trouble shooting There are two operating modes to select from MODE 1 Vacancy sensor Manual ON OFF Auto OF...

Page 2: ...ores to the length indicated by the Strip Gauge in Fig 3 approx 1 2 inch 4 Wire the sensor Twist the existing wires together with the wire leads on the RH 250 sensor s as indicated in either step 4a or 4b Cap wires securely using wire nuts a Wiring two RH 250s in a 3 way configuration Connect the green or non insulated copper GROUND wire from the circuit to the green terminal on each RH 250 Connec...

Page 3: ... 2 inch to expose the mode button and adjustment trimpots For multi way operation the Operating Mode and the Time Delay adjustments should be the same in all sensors related to the same load Setting up the Operating Mode Select the operating mode by pressing the Mode button The amber LED behind the switch button blinks to indicate the selected mode The blink pattern repeats three times One blink i...

Page 4: ...ted the TEST mode The controlled load turns ON for 5 seconds each time the sensor detects motion After 5 seconds expire without motion detection the load turns OFF The controlled load turns ON automatically with the next motion detection and stays ON for 5 seconds 4 Repeat as necessary to ensure that the desired coverage areas are within detection range You can do this test for each RH 250 in your...

Page 5: ...inte manuellement l activation automatique est réactivée lorsqu aucun mouvement n est détecté pendant 5 minutes Cela permet d éviter que la charge ne s active automatiquement après avoir été volontairement désactivée Temporisation La temporisation peut être sélectionnée par l utilisateur pendant la configuration Elle peut être réglée sur l une des valeurs fixes suivantes 15 secondes 5 minutes 15 m...

Page 6: ...lage au fil blanc du RH 250 auxiliaire Raccordez le fil d alimentation de la boîte de circuits SOUS TENSION au fil noir du RS 250 auxiliaire et au fil VA ET VIENT 1 Raccordez le fil VA ET VIENT 1 depuis le fil noir du RH 250 auxiliaire au fil noir du RH 250 maître Raccordez le fil d alimentation de la lampe CHARGE au fil rouge du RH 250 maître Scellez le fil rouge sur le RH 250 auxiliaire Connecte...

Page 7: ... d inoccupation marche arrêt manuels extinction automatique Deux clignotements indiquent le mode 2 fonctionnement détecteur de présence marche arrêt automatique avec commande manuelle et réinitialisation à la commande automatique après 5 minutes d inoccupation Pour changer le mode appuyez une fois sur le bouton Mode pour régler l appareil au mode 1 ou appuyez deux fois sur le bouton Mode pour régl...

Page 8: ...tecteur repère un mouvement Après 5 secondes passées sans détection la charge s éteint La charge contrôlée s active automatiquement lors de la prochaine détection et reste active pendant 5 secondes 4 Répétez les étapes autant de fois que nécessaire de sorte que le champ de détection soit conforme à la zone de couverture recherchée Vous pouvez effectuer ce test pour chaque RH 250 de votre configura...

Page 9: ...be presionar el botón de ENCENDIDO APAGADO para encender la carga Uno o varios RH 250s controlando una misma carga la mantendrán encendida hasta que ninguno de ellos detecte movimiento por un periodo de tiempo denominado Retardo de Apagado configurable desde 15 segundos hasta 30 minutos Existe un periodo de 30 segundos inmediatamente después de que la carga se ha apagado automáticamente durante el...

Page 10: ...le blanco del otro RH 250 denominado como auxiliar El término maestro es utilizado acá únicamente para designar el sensor que esta conectado directamente a la carga controlada Conecte el cable de LINEA o FASE del circuito al cable negro del RH 250 auxiliar y al cable VIAJERO 1 Conecte el cable VIAJERO 1 proveniente del cable negro del RH 250 auxiliar al cable negro del RH 250 maestro Conecte el ca...

Page 11: ...deará una ó dos veces según sea Modo 1 ó Modo 2 El LED repetirá el patrón seleccionado tres veces Después de eso la unidad estará programada para operar en el modo seleccionado Ajuste del Retardo de Apagado Gire la perilla izquierda en dirección contraria a las manecillas del reloj para reducir el tiempo que permanecerá encendida la carga después de la última detección de movimiento valor mínimo 1...

Page 12: ...zca inmóvil La carga controlada se apagará después de 5 segundos si el sensor no detecta movimiento 3 Movilícese dentro del área de cobertura La carga controlada se encenderá por 5 minutos cada vez que el sensor detecte movimiento Después de transcurridos 5 segundos de no detección la carga se apagará La carga se encenderá automáticamente con la próxima detección y se mantendrá encendida por otros...

Reviews: