5.3.2 Single circuit hydraulic installation: Parameter #4=SEP
Security Contact thermostat
Optionnal Return sensor
(Used when no RF thermostat is installed)
Supply water sensor
Main pump
Mixing 3 way valve
Boiler control
Water chillers signal
Heating Mode
Cooling mode
Heating demand output driving the boiler or
Stage 2 heating (if PE=yes)
Active (Contact closed) when the pump 1 is
active or when there is a domestic hot water
demand or PE=Yes with Ext Temp < PE t
Always OFF (Contact opened)
Cooling demand output driving a water chiller
Always OFF (Contact opened)
Active (Contact closed) when the pump 1 is
active
Pump 1 output with wired TH1 thermostat
Active if the thermostat is in heating demand
Active if the thermostat is in cooling demand
Pump 1 output with RF TH1 thermostat
Active if the thermostat is in heating demand
Active if the thermostat is in cooling demand
5.3.3 Dual circuit hydraulic installation: Parameter #4=2P.1 or 2P.2 with wired thermostat:
(*)
2P.1 with wired thermostats: Thermostat 2 for direct circuit is a non-reversible model (Contact when ambient temperature is below
setpoint). In cooling mode, the climatic control will automatically reverse the contact information.
2P.2 with wired thermostats: Thermostat 2 for direct circuit must be a reversible model (Contact when heat or cool demand).
2P.1 or 2P.2 with wired thermostat
Heating Mode
Cooling mode
Heating or cooling demand output informing the
heat pump or Stage 2 heating (if PE=yes)
Active (Contact closed) when the pump 1 or
pump 2 is active for heating circuits (IN1=TH1,
IN2=TH2) or PE=Yes with Ext Temp < PE t
Active (Contact closed) when the pump 1 or
pump 2 is active for cooling circuits (IN1=TH1,
IN2=TH2) or PE=Yes with Ext Temp < PE t
Pump 2 output
Active (Contact closed) if heat demand on direct
radiator circuit thermostat 2
Active (Contact closed) if cold demand on direct
radiator circuit thermostat 2 (*)
Pump 1 output
Active if the wired thermostat 1 is in heating
demand
Active if the wired thermostat 1 is in cooling
demand
Security Contact thermostat
HeatPump
signal
Aquastat
Pannel heater
pump 2
Supply water sensor
WFH Main pump1
Mixing 3 way valve
1
2
HP