23
Reset function
By keeping the
(OK)
key pressed for about 5 seconds all system parameters, time and day
of the week as well as user programs in
are reset to the factory setting. Established
radio configuration to rf thermostats, if any, is also erased. The cursor moves to
.
End
24
Press on the
(OK)
key to exit the installer menu and come back to the main menu in
mode.
7.2 Heating & Cooling curves
Fig. 9
7.3 Corresponding value for sensors.
To be checked with an ohmmeter with sensor unplugged.
Temperature (°C)
Resistance value (Ohm)
Temperature (°C)
Resistance value (Ohm)
-20°C
~94 k
40°C
~5,3 k
-10°C
~54 k
50°C
~3,6 k
0°C
~32 k
60°C
~2,5 k
10°C
~20 k
70°C
~1,8 k
20°C
~12,5 k
80°C
~1,3 k
30°C
~8 k
8.Technical Data / Materials
Measured temperature accuracy:
0,1 °C
Operating temperature:
0 - 50 °C
Flow temperature control range:
0 - 100 °C
Regulation characteristics:
Non-linear logarithmic PID control
Intelligent 3-point control (automatic detection of operating point)
Electrical protection:
Class II – IP 30
Supply voltage:
230 V (±10%), 50 Hz
Outside temperature (°C)