If PE = No 

 Conventional operation of the free 

contact "Heating output" (See Chap 5.3) 
If PE = Yes 

 See below explanations on “PE t”  

------------- 

PE t 

(Efficiency Point 
temperature 
setpoint) 

15

 

Setting the desired PE outdoor temperature. 
If PE = Yes 
• If the outdoor temperature is lower than the 
Efficiency Point temperature setpoint and if a 
heating request occurs, then the free contact of 
the “heating output” will be closed to control an 
auxiliary heat generator. 
• If the outdoor temperature is higher than the 
Efficiency Point temperature setpoint, and if a 
heating request occurs, then the free contact of 
the “heating output” will remain opened, forbidding 
to switch on a backup heat generator. 

-7°C 

 
 
-20°C to  
+ 15.0°C

 

 

 

 

16 

 

Temperature indication in 

°C or °F 

°

 

°F 

 

 

 

17 

Time indication mode 

24 hours or 12 hours 

 

24H 

 

12H Am/Pm 

 

 

18 

Side-track protection 

YES (ac- 

tive) 

 

NO (inactive) 

 

 

When YES is selected the pump and the auxiliary actuator are activated at midday 12 hrs, if they 
haven’t been active for a period of 24 hours. (12h00: Pump ON 1min, 12h01: Open actuator 2min, 
12:03: Close actuator 2min) 

 

The following parameter “

Pump

” is only used when no RF thermostats are installed and if no inputs (In1 & In2) 

are used for connecting box (C_b) and aquastat (Aqu) function. 

 

 

_ _ _  PUMP 

19 

Pump delay time: 

Time duration to switch off the pump 
after the stop demand from the 
wired thermostat or after complete 
close of the 3 way mixing valve. 
This function is also interesting to 
avoid permanent ON/OFF cycle of 
the pump when “PWM” thermostat is 

installed. 

030 

 

For best use 

the duration 

should be => 

2xPWM 

cycle 

of the thermo- 

stat 

 

 

001 to 060, 

and above 

“- - -“ 

= infinite delay, the 

pump will be ON 

all the time 

 

 

20 

Manual mode (or test function) for valve drive respectively 2/3-way valve 

By pressing the 

(+) 

key the valve drive opens. The display shows “OPEN“ and ▲. 

By pressing the 

(–) 

key the valve drive closes. The display shows “CLOSE“ and ▼ 

By pressing the 

(◄) 

or 

(►) 

key current position of the valve drive is kept. Displays “STOP“ 

 

There is a actuator security anti-short delay: when switching from “OPEN“ to “CLOSE“ 

or “CLOSE“ to “OPEN“, the actuator will be stopped during 15s 

 

Floor / screed preheating 
program. 

 

 

0 PrH 

 

7 PrH

 

_ _ _ 

PrH 

21 

The program is started by selecting „7 dry“ and runs automatically. 

 

For a period of 3 days the flow temperature is kept at 25 °C (days 7, 6, 5). For next 4 days the flow 
temperature is maintained at its preset maximum value (days 4, 3, 2, 1). 

 

The number of the days until the end of the heating program is displayed. 

 

Floor / screed dehumidifi- 
cation program 

0 drY 

Default value after “ON”

=> 

13 

Days 

7 to 60 days 

 

 

22 

The program is started by selecting the desired numbers of days and runs automatically. 

 

Example: 13 days selected: (3days rise + 7days at Hi + 3days decrease) 

For a period of 3 days the flow temperature will be increased up to the “

Hi

” value, then the tempera- 

ture will be kept at the “

Hi

” value during 7 days. For the last 3 days the temperature will be decreased 

up to the “

Lo

” value. 

Example2: 7 days selected: (3days rise + 1day at Hi + 3days decrease) 

 

The number of the days left until the end of the fllor dehumidification program is displayed. 

Summary of Contents for RCL-HC

Page 1: ...GB 1 Climatic Control H C User Guide PPLIMW08157Ch EN wattswater eu ...

Page 2: ...e shops approved by the manufacturer only The functionality of the control depends on the model and equipment This installation leaflet is part of the product and has to be obtained Subject to technical modification Table of content 1 Application 3 2 References Symbols and Abbreviations 3 3 Safety Instructions 3 4 Display 4 5 Installation and Electrical connections 4 5 1 ClimaticControl HC Install...

Page 3: ... better understanding in this document references are used in the form of symbols and abbreviations which are described below Reference to further documents FlH Floor heating Important information and application hints RaH Radiant heating general Safety information or Important information about functions FRG Hydraulic control unit with pump and mixing valve OK button OK HKV Manifold Control butto...

Page 4: ... for example FRG or FlowBox and if it is not attached to that unit by any installation plate or support it should be installed next to that unit Pay attention to the correct connection of the cables if the ClimaticControl HC is not installed directly on a hydraulic control unit but at some other place for the reason of better access Refer to the directions about this in section 5 2 Electric connec...

Page 5: ...ed sensor Possible RF Outdoor sensor in option 3 Point actuator WATTS EVO2 Cooling output 230VAC 50Hz or P2 Pump 230 VAC 50 Hz Direct circuit L N Fig 5a Heating output Heating demand for the boiler Free contact N L N Option Optional connection temperature limiter TB option for pump1 only The connection is factory fitted with a cable bridge It must be removed if connecting TB Logical inputs o 2 o 4...

Page 6: ... Yes with Ext Temp PE t Always OFF Contact opened Cooling demand output Pump 2 output driving a 3 way On Off valve to choose between Heating or cooling water Always OFF Contact opened HOT Always ON Contact closed COLD Pump 1 output with wired TH1 thermostat Active if the thermostat is in heating demand Active if the thermostat is in cooling demand Pump 1 output with RF TH1 thermostat Active if the...

Page 7: ...1 with wired thermostats Thermostat 2 for direct circuit is a non reversible model Contact when ambient temperature is below setpoint In cooling mode the climatic control will automatically reverse the contact information 2P 2 with wired thermostats Thermostat 2 for direct circuit must be a reversible model Contact when heat or cool demand 2P 1 or 2P 2 with wired thermostat Heating Mode Cooling mo...

Page 8: ...tic hot water demand through Aquastat input IN1 or IN2 OR PE Yes with Ext Temp PE t Active Contact closed when the pump 1 or pump 2 is active for cooling circuits OR PE Yes with Ext Temp PE t Pump 2 output Active Contact closed if heat demand on direct radiator circuit RF thermostat 2 Active Contact closed if cold demand on direct radiator circuit RF thermostat 2 Pump 1 output Active if the RF the...

Page 9: ...p switches off after pump delay time PUMP System parame ters pump delay time WFHT BASIC WFHT LCD MILUX xxx 5 4 2 Direct circuit Panel Heater standard room thermostat wired type If a second circulation pump is installed and managed by the ClimaticControl HC Inst System param eters installation type 2P x you can install a second wired room thermostat to manage the working of the high temperature pum...

Page 10: ... 1 C upper the setting temperature of the thermostat If a Milux RF Hygrostat is used the program feature See Chapter Error Reference source not found is deported on the thermostat user interface 5 4 4 Wireless room Hygrostat Water Floor thermostat trF1 If a radio frequency room Hygrostat is plugged in the flow temperature calculated on the basis of outdoor temperature and the curve flow temperatur...

Page 11: ...e to the Wireless outside sensor the regulation will continue to work with the last value received from the out side sensor 5 4 7 Inputs functions In1 In2 If no wired thermostat is installed in the house you will have the possibility to use the two available inputs of your ClimaticControl HC for different functions Inst System parameters Input In1 In2 1 Input1 Inst System parameters Input HC You c...

Page 12: ...The heating output will stay activated even if the aquastat have stopped the circulation pump To avoid problem in cooling mode if the storage tank is filled with cold water by heat pump the aquastat function will be automatically desactivated Inst System parameters Input C_b In case of mutizone regulation WFHC Master RF with Heat Cool function is installed you could use the input 2 to connect the ...

Page 13: ...llation with 2 circulation pumps Under floor heating and panel heater In1 used to stop the pump when the heat storage is empty Inst Parameters menu In1 Aqu In2 used to stop the pump when the heat storage is empty Inst Parameters menu In2 Aqu In2 Immersion thermostat Use to stop the pump2 T C In1 Immersion thermostat Use to stop the pump1 T C Fig 12 Pump signal closed pump On WFHC Aquastat storage ...

Page 14: ... ClimaticControl HC becomes lower than the actual tempera ture value because of rising outdoor temperatures If the actual value of the flow temperature falls below the preset value the pump will restart In this case to ensure a correct measure of the water temperature the pump will be start each 30min for a short time to measure the real temperature of water inside the hydraulic circuit To ensure ...

Page 15: ...acted to the calculated water temperature willbe always adjusted on the both working mode of the CC HC 0 00 C 10 0 C by default For the operation of the circulation pump please refer to the section of COMFORT mode of operation REDUCED TEMPERATURE mode of operation Unlimited operation in REDUCED TEMPERATURE mode This is a constant mode of operation of the system The ClimaticControl HC adjusts the f...

Page 16: ...e on the ClimaticControl HC Because in this case the regulation will not work in the correct way TIME AND DATE setting In this menu you can set the actual time and date as well as the day of the week Using the cursor select first and then press the OK key By keys or set the minutes confirm by pressing OK By keys or set the hour confirm by pressing OK By keys or set the day of the week press OK to ...

Page 17: ...g the programming of the last day 7 the indication first switches to the program menu and in about 15 seconds back to If during programming no inputs are made within 20 seconds indication switches first to the program menu and in another 15 seconds it returns to The inputs were not stored Factory built in programs P1 P9 If you select any of the factory programs from P1 to P9 you confirm it by pres...

Page 18: ...d to set the most important parameters for the operation of the system To access this menu keep the OK key pressed for 10 seconds in Comfort Auto Reduced modes The display shows as well as the preset curve for example Parameters are selected by pressing the or keys To change the parameters press ОК and using or change them To leave the menu goes to the parameter End and press the OK key ...

Page 19: ...set above Cooling parameters 1 Cooling curve value see fig 7 supplied water T curve outside T 0 4 0 1 to 5 2 Maximum value of flow temperature in Cooling mode 30 C Lo 5 C 100 C 3 Minimum value of flow temperature in Cooling mode 15 C 1 Hi 1 C Remark The thermostat has the priority over the water law limits on the pump and cooling outputs Thus the 3 way valve will always follow the limits set above...

Page 20: ...s mounted on the return pipe of the hydraulic circuit _ _ _ b AP 7 bGAP Boost function The incoming water temperature will be increased by 20 if the return temperature is less than calculated water temperature minus bGAP set ting Wret Wcal bGAP WCal 20 Press on the OK to view the instan taneous value of the return sensor Remark if no water return sensor is wired then this boost function is bypasse...

Page 21: ...use th parameter is set to YES no Input1 not used nothing wired no th1 un adjustable no Aqu HC or C_b Aqu A water Aquastat contact is wired on Input1 If over temperature is reached contact open then Pump1 circulator is stopped and the mixing valve is closed HC A Heat Cool switching signal is wired on In put1 to manage the working mode of the in stallation contact between point 2 and In1 or phase s...

Page 22: ...es Wired outside sensor is installed No Installation without outside sensor The regulation will work like a thermostat with a adjustable Wcal temperature injected on the circuit rF Wireless RF outside sensor is installed Yes No rF The following parameter is only available if no outside sensor is installed and the OUSE parameter is set to no _ _ _ OU t 14 Outside temperature This menu is used to fi...

Page 23: ...rmanent ON OFF cycle of the pump when PWM thermostat is installed 030 For best use the duration should be 2xPWM cycle of the thermo stat 001 to 060 and above infinite delay the pump will be ON all the time 20 Manual mode or test function for valve drive respectively 2 3 way valve By pressing the key the valve drive opens The display shows OPEN and By pressing the key the valve drive closes The dis...

Page 24: ...ing value for sensors To be checked with an ohmmeter with sensor unplugged Temperature C Resistance value Ohm Temperature C Resistance value Ohm 20 C 94 k 40 C 5 3 k 10 C 54 k 50 C 3 6 k 0 C 32 k 60 C 2 5 k 10 C 20 k 70 C 1 8 k 20 C 12 5 k 80 C 1 3 k 30 C 8 k 8 Technical Data Materials Measured temperature accuracy 0 1 C Operating temperature 0 50 C Flow temperature control range 0 100 C Regulatio...

Page 25: ...e to incorrectly con nected valve drive reverse action Check the connection of the valve drive 5 2 2 3 Too low flow temperature due to incorrectly con nected valve drive reverse action Check the connection of the valve drive 5 2 2 4 Incorrect selected operation mode Select the correct mode of operation 2 5 When ClimaticControl HC operating in AUTO MATIC mode incorrect programming of built in or us...

Page 26: ......

Page 27: ......

Page 28: ...PLIMF08157Ch EN ...

Reviews: