background image

2

Teflon

® 

is a registered trademark of E.I. Dupont de Nemours 

& Company.

Installation Precautions

•   Do NOT install system on line pressure above 90psi.
•   Do NOT install system on HOT water line. Failure to limit 

line temperature to 100°F may result in housing failure 

and damage.

•   Do NOT install the system backwards with the feed water 

line connected to the outlet.

•   Do NOT use liquid pipe compounds for fitting connections. 

USE two to three wraps of Teflon

®

 tape.

•   Do NOT solder plumbing connections attached to filter 

housing or inlet valve. Inlet valve and filter housing will be 

damaged by high temperature.

•   Do NOT allow system to freeze. Turn off water supply to 

housing and drain housing if temperature falls below 40°F.

•   Do NOT install system in direct sunlight or where system is 

exposed to harsh chemicals or may be subjected to being 

struck by moving equipment, carts, mops or any other item 

that may cause damage.

•   ALLOW a minimum of 3” under the housing to allow for 

filter replacement.

•   IF water hammer is evident, install water hammer arrestors 

before the OneFlow

®

 unit. 

•   Do NOT overtighten fitting connections into inlet valve 

or housing outlet. 

•   Always back-up valves and fittings with a wrench when  

installing a fitting to avoid turning the valve.

•   Do NOT install the unit behind equipment where it may 

be difficult to access the system for filter replacement.

•   Position the OneFlow

®

 unit in a suitable location. 

•   The direction of flow through the OneFlow

®

 unit is always 

through the inlet first; keep this in mind when determining 

installation location.

•   Do NOT mount the OneFlow

®

 system near any source of 

heat. 

•   DO NOT mount the system above any device or area that 

would be adversely effected by water. 

WARNING

!

•   Do not discard this manual after installation. This manual 

contains important operation, maintenance and precaution-

ary information. Please present this manual to user/operator/

owner after installation.

•   It is strongly encouraged that you read this manual before 

installing the system to ensure the best possible installation.

•   Installation must conform to all local and state plumbing 

codes and regulations.

•   Notice to user/operator/owner: Please retain this manual for 

future reference for parts, maintenance or troubleshooting.

•   It is recommended that all personnel responsible for operation 

and maintenance of this product read the precautions, 

operation and maintenance sections of this manual.

NOTICE

NOTICE

  *  Systems using OneFlow

®

 technology are effective at con-

trolling lime-scale formation inside the plumbing system at 

influent hardness levels up to 30 grains per gallon (513 ppm 

CaCO3) of calcium carbonate. Due to variances in water 

chemistry, 30 grains per gallon is a recommended hard-

ness maximum due to potential aesthetic issues related to 

soft scale residue formation outside of the plumbing system. 

Testing should be performed to determine proper application 

where hardness levels exceed 30 grains per gallon.

  ** Just as with conventional water softening media, OneFlow

®

 

media needs to be protected from excess levels of certain 

metals that can easily coat the active surface, reducing its 

effectiveness over time. Public water supplies rarely, if ever, 

present a problem, but if the water supply is from a private 

well, confirm that the levels of iron (Fe) and manganese (Mn) 

are less than 0.3 mg/L and 0.05 mg/L, respectively.

*** Pursuant to the EPA drinking water standards, the copper 

concentration permitted is up to 1.3 ppm. Typically originat-

ing from new copper plumbing, high levels of copper can 

foul OneFlow media. New Copper lines need to be pas-

sivated for a minimum of 4 weeks before placing unit into 

service. For applications with copper concentration greater 

than 1.3 ppm, please consult Watts Water Quality Technical 

Service. To further minimize any problem with excess cop-

per, avoid applying excessive flux on the inner surfaces of 

the pipe and use a low-corrosivity water soluble flux listed 

under the ASTM B813 standard.

 

 

 

WARNING

!

Feed Water Chemistry Requirements

pH

6.5-8.5

Hardness (maximum)

30 grains (513 ppm CaCO3) *

Water Pressure

15 psi to 90 psi (1.03 bar to 6.2 bar)

Temperature

40° F to 100° F (5°C to 38°C)

Free Chlorine

<2 ppm

Iron (maximum)

0.3 ppm **

Manganese (maximum)

0.05 ppm **

Copper

1.3 ppm***

Oil & H2S

Must be Removed Prior to OneFlow

Total Phosphates

< 3.0 ppm

Silica (maximum)

20 ppm †

TDS

1500 mg/l ††

NOTICE

† OneFlow

®

 media does not reduce silica scaling. While silica 

tends to have a less significant effect on scale formation than 

other minerals, it can act as a binder that makes water spots 

and scale residue outside the plumbing system difficult to 

remove. This 20 ppm limitation is for aesthetic purposes.
†† All other contaminants must meet the requirements of the 

USEPA Safe Drinking Water Act. Specific Mineral and Metal 

MCL's, identified in Watts published Feed Water Chemistry 

Requirements, supersedes the USEPA SDWA.
Water known to have heavy loads of dirt and debris may require 

pre-filtration prior to OneFlow

®

.

Summary of Contents for OneFlow OFTWH-C

Page 1: ...pecifications Inlet Outlet Connections 3 4 FNPT 19 05 mm Nominal Flow Rate up to 5 gpm 18 92 lpm Maximum Pressure 90psi 6 2 bar Maximum Temperature 100 F 38 C Minimum Temperature 40 F 5 C Capacity OFTWH C RM cartridge does not have a grain removal capacity however other contaminants present in the water will gradually degrade the effectiveness of this cartridge Change the OFTWH C RM cartridge at l...

Page 2: ...tenance sections of this manual NOTICE NOTICE Systems using OneFlow technology are effective at con trolling lime scale formation inside the plumbing system at influent hardness levels up to 30 grains per gallon 513 ppm CaCO3 of calcium carbonate Due to variances in water chemistry 30 grains per gallon is a recommended hard ness maximum due to potential aesthetic issues related to soft scale resid...

Page 3: ... leaks 8 If a drain valve was not installed on the outlet side of the system hold the tubing that will connect to equipment in a clean bucket or over sink or drain Open the system inlet feed valve and allow water to flush through system for 2 minutes at the specified system flow rate to allow air bubbles to escape NOTE NO ACTIVATION IS REQUIRED FOR THE OneFlow SYSTEM TO PERFORM PROPERLY FLUSHING I...

Page 4: ...if equipped and flush the new cartridge to drain or bucket for two 2 minutes or until water runs clear If no flush valve is present disconnect line from equipment to flush to drain 10 VERY IMPORTANT With water supply inlet valve OPEN and water flow confirmed turn on connected equipment Failure to supply water to equipment may cause serious damage 11 Record filter change on the service log Maintena...

Page 5: ... 3 4 ports w PR 1a 7300398 Full Flow O ring 2 7300845 Ball Valve PVC 3 4 F x M 3 7100466 Full Flow Mounting Bracket 4 7300395 Mounting Screws 5 0002192 OFTWH C RM Replacement Cartridge 6 N R Pressure Relief Button part of housing 7 7100299 Full Flow Housing Wrench not shown IN OUT inlet outlet 4 6 5 1 1a 2 3 4X ...

Page 6: ...r valve is limited to furnishing a replacement for or at our option repairing any part or parts to our satisfaction that prove defective within the warranty period stated above Such replacement parts will be delivered to the owner F O B nearest factory at no cost excluding freight and local labor charges if any Our obligation under this warranty with respect to the OneFlow media will be limited to...

Page 7: ......

Page 8: ...tien régulier vous profiterez d un fonctionnement sans souci pendant des années Veuillez vous reporter à ce manuel lorsque vous effectuez les changements de filtre réguliers Les directives facilitent et accélèrent l entretien périodique afin que vous puissiez tirer le maximum de votre système Spécifications du système Raccords d entrée de sortie 3 4 po FNPT 19 05 mm Débit nominal maximal de 5 gal ...

Page 9: ...AVIS Les systèmes utilisant la technologie OneFlow sont efficaces pour contrôler la formation de tartre à l intérieur du système de plomberie à des niveaux de dureté influent jusqu à 30 grains par gallon 513 ppm CacO3 de carbonate de calcium En raison des variations de la chimie de l eau 30 grains par gallon est un maximum de dureté recommandée en raison de problèmes esthétiques potentiels liés à ...

Page 10: ...ôté sortie du système tenez la tuyauterie qui sera raccordée à l équipement dans un seau propre ou sur l évier ou un drain Ouvrez la vanne d alimentation d entrée du système et laissez l eau rincer le système pendant deux 2 minutes au débit indiqué afin d évacuer les bulles d air REMARQUE AUCUNE ACTIVATION REQUISE POUR QUE LE SYSTÈME OneFlow FONCTIONNE CORRECTEMENT LA VIDANGE EST RECOMMANDÉE POUR ...

Page 11: ...uipé et rincez la nouvelle cartouche dans le drain ou le seau pendant deux 2 minutes ou jusqu à ce que l eau soit claire S il n y a pas de robinet de rinçage détacher la conduite de l équipement pour vidanger dans le drain 10 TRÈS IMPORTANT le robinet d entrée de l alimentation d eau étant OUVERT et en présence d un débit d eau mettez l équipement connecté sous tension L équipement pourrait être g...

Page 12: ...ec PR 1a 7300398 Joint torique plein débit 2 7300845 Clapet à bille PVC 3 4 po F x M 3 7100466 Support de montage plein débit 4 7300395 Vis de montage 5 0002192 OFTWH C RM Cartouche de remplacement 6 N R Bouton de libération de pression partie du boîtier 7 7100299 Clé de boîtier plein débit non illustré IN OUT inlet outlet 4 6 5 1 1a 2 3 4X ...

Page 13: ...ions Notre obligation en vertu de la présente garantie par rapport au réservoir ou à la vanne est limitée à fournir un remplacement pour ou selon notre option la réparation de l ensemble des pièces ou d une pièce à notre satisfaction qui se révèle révèlent défectueuse s pendant la période de garantie indiquée ci dessus Ces pièces de rechange seront livrées au propriétaire FAB à l usine la plus pro...

Page 14: ......

Page 15: ...tes del envío Con la instalación y el mantenimiento de rutina adecuados tendrá años de funcionamiento sin problemas Consulte este manual cuando realice cambios de filtro rutinarios Las instrucciones facilitan y agilizan el mantenimiento periódico y se aseguran de que usted reciba el máximo beneficio de su sistema Especificaciones del sistema Conexiones de entrada salida 3 4 FNPT 19 05 mm Caudal no...

Page 16: ... la acumulación de sarro cal dentro del sistema de fontanería a niveles de dureza influyente de hasta 30 granos por galón 513 ppm CaCO3 de carbonato cálcico Debido a las variaciones en la química del agua 30 granos por galón es el máximo de dureza recomendado debido a posibles problemas estéticos relacionados con la formación de residuos de sarro fuera del sistema de fontanería Las pruebas deben r...

Page 17: ... drenaje en el lado de la salida de sistema sostenga el tubo que se conectará al equipo en una cubeta limpia o sobre el fregadero o el drenaje Abra la válvula de alimentación de entrada del sistema y deje que el agua se fluya a través del sistema durante 2 minutos a la velocidad de flujo del sistema especificada para permitir que se escapen las burbujas de aire NOTA NO SE REQUIERE ACTIVACIÓN PARA ...

Page 18: ... y descargue el nuevo cartucho para drenarlo o ponerlo en un balde por dos 2 minutos o hasta que el agua salga transparente De no contener una válvula de descarga desconecte la línea del equipo para descargar y drenar 10 MUY IMPORTANTE encienda el equipo conectado con la válvula de entrada del suministro de agua ABIERTA y el flujo de agua confirmado Si no se le suministra agua al equipo se pueden ...

Page 19: ... 3 4 con PR 1a 7300398 Junta tórica de flujo completo 2 7300845 Válvula de bola PVC 3 4 F x M 3 7100466 Soporte de montaje de flujo completo 4 7300395 Tornillos de montaje 5 0002192 Cartucho de repuesto OFTWH C RM 6 N R Botón de liberación de presión parte del bastidor 7 7100299 Llave de bastidor de flujo completo no se muestra IN OUT inlet outlet 4 6 5 1 1a 2 3 4X ...

Page 20: ... que se comprobaron defectuosas dentro del período de garantía antes mencionado Dichas piezas de reemplazo se entregarán a la fábrica F O B más cercana del dueño sin costo alguno excluyendo cargos por fletes y trabajos locales de presentarse Nuestra obligación según la presente garantía con respecto a la sustancia de OneFlow se limitará a facilitar un reemplazo por la sustancia en un plazo de dos ...

Reviews: