SECTION 4:
INITIAL START-UP
4.1 INITIAL START-UP REQUIREMENTS
The following are the prerequisites for the initial start-up of the Benchmark boiler:
•
Complete the installation per the
Benchmark Platinum-Edge: INSTALLATION Manual
(GF-210), including gas supply piping, vent installation and condensate drain piping.
Starting a unit without the proper piping, venting, or electrical systems can be dangerous
and may void the product warranty.
•
Set proper controls and limits (see Section 2:
EZ Setup
or
Section 6:
Advanced Setup
in
the
Edge Controller Manual
).
Initial start-up consists of the following:
•
Combustion calibration (Section 4.4:
Combustion Calibration
)
•
Test safety devices (Section 5:
Safety Device Testing
)
Start-up must be successfully completed before putting the unit into service. The start-up
instructions below should be followed precisely in order to operate the unit safely and at high
thermal efficiency and low flue gas emissions.
Initial unit start-up
must be
performed by AERCO factory trained personnel, who are trained in
the start-up and service of Benchmark boilers.
An AERCO Gas Fired Startup Sheet, included with each Benchmark unit, must be completed
for each unit for warranty validation and a copy must be returned promptly to AERCO via e-mail
at:
.
WARNING!
DO NOT ATTEMPT TO DRY FIRE THE UNIT.
Starting the unit without a full water level can
seriously damage the unit and may result in injury to personnel and/or property damage. This
situation will void any warranty.
NOTE:
AERCO recommends that the
Standby Blower Voltage
parameter be kept at 2.00 volts (the
default set at the factory) to prevent flue gas recirculation.
To check, go to the Controller’s
Main Menu
Advanced Setup
Performance
Fire
Control
Operating Control
and verify that the
Standby Blower Voltage
parameter is set
to
2.00 V
.
However, individually vented units in positive pressure boiler rooms may set
Standby
Blower Voltage
between
2.00
and
0
volts to compensate.