Benchmark Platinum-Edge: Operation-Service Manual
SECTION 9 – AERTRIM OPERATION
OMM-0137_D • GF-211
•
7/16/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 126 of 146
BMK 2000 AERtrim Values
MENU ITEM
Minimum
Maximum
Default
Settle Time
0
120 Sec
20 Sec
Trim Gain
0.1
5.0
0.250
Max Tries
0
100
15
O
2
Target
(must be
between O
2
Upper & O
2
Lower)
18%
3%
8%
6.5%
30%
3%
8%
6.0%
40%
3%
8%
6.0%
50%
3%
8%
5.5%
70%
3%
8%
5.5%
100%
3%
8%
5.0%
O
2
Lower
(must be at
least 1%
lower than
O
2
Upper)
18%
2.5%
5.5%
5.0%
30%
2.5%
5.5%
5.5%
40%
2.5%
5.5%
5.5%
50%
2.5%
5.5%
5.0%
70%
2.5%
5.5%
5.0%
100%
2.5%
5.5%
4.5%
O
2
Upper
(must be at
least 1%
higher than
O
2
Lower)
18%
5.5%
8.5%
7.0%
30%
5.5%
8.5%
6.5%
40%
5.5%
8.5%
6.5%
50%
5.5%
8.5%
6.0%
70%
5.5%
8.5%
6.0%
100%
5.5%
8.5%
5.5%
O
2
Offset
-3.0
3.0
1.0
BMK 2000 AERtrim Adjustment Range
CALIBRATION POINT
BLOWER VOLTAGE
Minimum
Maximum
Default
18%
1.90
4.00
1.40
30%
2.70
7.70
3.80
40%
3.00
7.70
4.30
50%
3.30
7.70
5.40
70%
4.00
9.60
6.40
100%
6.00
10.00
9.50