Benchmark 750-3000 Installation & Startup Manual
SECTION 2
– INSTALLATION
OMM-115_D
•
GF-200
•
5/9/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 28 of
126
2.9.3 External Gas Supply Regulator
An external gas pressure regulator is required on the gas inlet piping under most conditions
(see, below). Regulators must conform to the specifications shown in the tables below.
The external natural gas regulator must be capable of regulating the following BTU per hour
while maintaining the minimum gas pressure listed below:
TABLE 2-3a: NATURAL GAS Regulator Capacity
Model
BTU/HR (kW)
Minimum Gas Pressure
BMK 750/1000
49,000
–
1,020,000 (14.3
– 299)
4.0” W.C. (1.0 kPa)
BMK 1500
100,000
– 2,120,000 (29.3 - 621.3) 4.0” W.C. (1.0 kPa)
BMK 2000
100,000
– 2,120,000 (29.3 - 621.3) 4.0” W.C. (1.0 kPa)
BMK 2500/3000
150,000
– 3,180,000 (44 - 932)
4.0” W.C. (1.0 kPa)
TABLE 2-3b: PROPANE Gas Regulator Capacity
Model
BTU/HR (kW)
Minimum Gas Pressure
BMK 750/1000
49,000
–
1,020,000 (14.3
– 299)
11.0” W.C. (2.74 kPa)
BMK 1500/2000
100,000
– 2,120,000 (29.3 - 621.3) 4.0” W.C. (1.0 kPa)
BMK 2500/3000
150,000
– 3,180,000 (44 - 932)
4.0” W.C. (1.0 kPa)
A lock-up style regulator
MUST
be used when gas supply pressure will
exceed
14” W.C. (3.49
kPa).
2.9.3.1 Massachusetts Installations Only
For Massachusetts installations, a mandatory external gas supply regulator must be
positioned as shown in Figure 2-7a, 2-7b and 2-7c. The gas supply regulator must be
properly vented to outdoors. Consult the local gas utility for detailed requirements concerning
venting of the supply gas regulator.
2.9.3.2 All Installations (Except Massachusetts)
For installations with 3 or more units (other than Massachusetts) that
EXCEED
7” W.C. (1.7
kPa)
gas pressure, a separate external gas supply regulator, as shown in Figure 2-7a, 2-7b
and 2-7c,
is highly recommended
. No regulator is required for gas pressures
below
7”
W.C.
(1.7 kPa)
of pressure. Consult the local gas utility for detailed requirements concerning
venting of the supply gas regulator.
NOTE:
It is the responsibility of the customer to source and purchase the appropriate gas regulator as
described above. However, AERCO offers for sale an appropriate regulator, which may be
ordered at the time of unit purchase or separately. Contact your AERCO sales representative
for more information.