13
Multi-function
output
61
Multi-output 1 (terminal 11 & 10) 00 : Run mode
01 : Up to desired freq.
02 : Set freq. Fout = Fn_08+/-Fn_09
03 : Freq. detection Four > Fn_08
04 : Freq. detection Four > Fn_08
05 : Over torque detection
06-11 : Change 00-05 from (N/O) to
(N/C)
00
62
Reserved
63
Reserved
64
Reserved
Prohibit Freq.
65
Setting prohibited freq. 1
0.01 Hz
0-400 Hz
0 Hz
control
66
Setting prohibited freq. 2
0.01 Hz
0-400 Hz
0 Hz
67
Setting prohibited freq. 3
0.01 Hz
0-400 Hz
0 Hz
68
Setting prohibited freq. range
0.01 Hz
0-10 Hz
0 Hz
Electronic
thermal
protection
69
xxx0 : Electronic thermal motor protection enable
xxx1 : Electronic thermal motor protection disable
xx0x : Electronic thermal characteristics in accordance with standard m.
xx1x : Electronic thermal characteristics in accordance with special
motor
x0xx : Inverter protection OL : 103 % continues 150 % for one minute
x1xx : Inverter protection OL : 113 % continues 123 % for one minute
0xxx : Free run to stop after electronic thermal motor protection is
energized
1xxx : Operation continued after electronic thermal motor protection is
energized
0000
Electronic
thermal overload
reference current
70
Motor rated current
0.1 A
depend on
motor spec.
Torque boost
control
71
x0xx : Torque boost enable
x1xx : Torque boost disable
1xxx : Manual torque boost
72
Torque boost gain
0.1 %
0.0-10.0 %
0.0 %
*1
73
Reserved
74
Reserved