11
Momentary
power loss
31
Momentary power loss ride
through time
0.1 sec
0-2 sec
0.5 sec
32
xxx0 : Disable
xxx1 : Enable
0
33
Reserved
Auto restart
34
Auto restart interval
0.1 sec
0-800 sec
0 sec
35
No. of auto restart attempt
1
0-10
0
Motor pole
36
No. of motor poles
2 P
2-8 pole
4P
V/F pattern
37
Max. freq.
0.01 Hz
50-400 Hz
60 / 50 Hz
*4
38
Max. voltage ratio
0.1%
0-100%
100%
*4
39
Mid. freq.
0.01 Hz
0.11-400 Hz
3.0 / 2.5Hz
40
Mid. voltage ratio
0.1%
0-100%
7.5 %
41
Voltage ratio at 0.1 Hz
0.1%
0-100%
7.5%
Start freq.
42
Start freq. adjustment
0.01 Hz
0.1-10 Hz
1 Hz
Carrier freq.
43
Carrier freq. adjustment
1
0-15
14
Stopping mode
& braking
resistor
protection
44
xxx0 : Decel. to stop
xxx1 : Free run to stop
xx0x : Braking resistor overheat protection disable
xx1x : Braking resistor overheat protection enable
0000
Multi-function
analog output
45
Gain of multi-function analog
output
1%
0-200 %
100%
*1
selection
(terminal 15 &
16)
46
0 : Output freq. (Fn 6 max.)
1 : Set freq. (Fn 6 max.)
2 : Output voltage (Vac)
3 : DC voltage (Vpn)
0 *1
Display mode
47
xxx0 : Output voltage (Vac) display disable
xxx1 : Output voltage (Vac) display enable
xx0x : DC voltage display disable
xx1x : DC voltage display enable
x0xx : Output current (Iac) display disable
x1xx : Output current (Iac) display enable
0000 *1