38
3. Fn_82 = xx01, Fn_56 - Fn_58 = 08: If multi-function input terminal is ON, output voltage will
decrease gradually (to previous output voltage x Fn_83). When the input terminal is off, output
voltage will increase to previous voltage gradually.
Remark: The speed of above mentioned voltage goes up or down is the same as that of speed search.
Fn_84 - Fn_91 : Please refer to Fn_17
Vibration prevention control (Fn_92 - Fn _94)
Fn_92 : Vibration prevention times : 1 - 100
Fn_93 : Vibration prevention gain : 0 - 100 %
Fn_94 : Vibration prevention bias
: 0 - 30 %
1. Adjusting Fn_92 (unit : 2ms) to 1/4 of machine‘s vibration cycle can provide the optimal
performance.
2. Adjusting Fn_93 according to the amplitude of vibration can reduce vibration to minimum.
Fn_95 : Reserved
Fn_96 : Reserved
Fault contact control (Fn_97 - Fn_98)
Fn_97 : xxx0 - Fault contact is not energized during auto restart operation
xxx1 - Fault contact is energized during auto restart operation
xx0x - Fault contact is not energized during momentary power loss detection
xx1x - Fault contact is energized during momentary power loss detection
x0xx - Fault contact is not energized after external emergency stop signal is received
x1xx - Fault contact is energized after external emergency stop signal is received
0xxx - Fault contact is not energized during external baseblock
1xxx - Fault contact is energized during external baseblock
Fn_98 : xxx0 - Fault contact is not energized after overtorque (OL3) is detected
xxx1 - Fault contact is energized after overtorque (OL3) is detected
xx0x - Fault contact is not energized after electronic thermal motor protection (OL1)
is activated
xx1x - Fault contact is energized after electronic thermal motor protection (OL1) is
activated