30
Multi-function output on TM2 is 0 ~ 10 VDC analog output, Output mode can be set by Fn_46.
Function of Fn_45 is as follows:
1. Fn_45 can be used to calibrate external meters or other peripherals.
Fn_47 : Refer to Fn_36
Dynamic braking and priority of stopping and speed search and AVR control
Fn_48 = xxx0 : Enhanced braking capacity.
= xxx1 : Standard braking capacity
= xx0x : Stop key effective in remote control mode
= xx1x : Stop key ineffective in remote control mode
= x0xx : Speed search controlled by terminals on TM2
= x1xx : Speed search effective when inverter start
= 0xxx : AVR function effective
= 1xxx : AVR function ineffective
1. Fn_48 = xxx0, Inertia energy of load can be used up by motor via output voltage adjustment
during deceleration.
2. Fn_48 = xx0x, “STOP” key on digital operator can be used for emergency stop even during
remote control (Stopping mode set by Fn_44); External switch must be turned OFF then ON
again for restarting inverter.
3. Fn_48 = x0xx, Speed search will be effective if multi-function input Fn_56 - 58 are 07 or 23
and multi-function input terminal operated, otherwise, inverter will start based on start
frequency (Fn_42)
4. Speed search will search from preset frequency during operation.
5. Please refer to FN_05( V/F pattern) for AVR function.
Fn_49, Fn_50 : Please refer to Fn_01
Fn_51, Fn_52 : Please refer to Fn_36
Fn 53 - Fn_55 : Please refer to Fn_44
Multi function input (Fn 56 - Fn_60)
00 : SP1 (Multi-speed 1)
:
Please refer to Fn_17
01 : SP2 (Multi-speed 2)
:
Please refer to Fn_17
02 : SP3 (Multi-speed 3)
:
Please refer to Fn_17
03 : Jog operation
:
Please refer to Fn_17