background image

0600-0066-0000 Rev. E

  

Made in the U.S.A.

April 2013

 

1 2

3 4

EZ-ZONE

®

 

PM Express

User's Guide

Registered Company

Winona, Minnesota  USA

ISO 9001

TOTAL

3 Year Warranty

CUSTOMER

SATISFACTION

Limit Controller

1241 Bundy Boulevard., Winona, Minnesota USA 55987

Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507  http://www.watlow.com

L

I

M

I

T

L

I

M

I

T

L

I

M

I

T

RESET

RESET

RESET

Safety Information

We use note, caution and warning symbols throughout 

this book to draw your attention to important opera-

tional and safety information.

A “NOTE” marks a short message to alert you to an 

important detail.

A “CAUTION” safety alert appears with information 

that is important for protecting your equipment and 

performance. Be especially careful to read and follow 

all cautions that apply to your application.

A “WARNING” safety alert appears with informa-

tion that is important for protecting you, others and 

equipment from damage. Pay very close attention to 

all warnings that apply to your application.

The electrical hazard symbol, 

 (a lightning bolt in a 

triangle) precedes an electric shock hazard CAUTION 

or WARNING safety statement. Further explanations 

follow:

Symbol

Explanation

CAUTION – Warning or Hazard 

that needs further explanation 

than label on unit can provide.  

Consult users manual for further 

information.

ESD Sensitive product, use proper 

grounding and handling techniques 

when installing or servicing 

product.

Unit protected by double/rein-

forced insulation for shock hazard 

prevention.

Do not throw in trash, use proper 

recycling techniques or consult 

manufacturer for proper disposal.

Unit can be powered with either 

alternating current (ac) voltage or 

direct current (dc) voltage.

Unit is a Listed device per Un-

derwriters Laboratories®.  It has 

been evaluated to United States 

and Canadian requirements for 

Process Control Equipment.  UL 

61010 and CSA C22.2 No. 61010.  

File E185611 QUYX, QUYX7.  See: 

www.ul.com

Unit is compliant with European 

Union directives.  See Declaration 

of Conformity for further details on 

Directives and Standards used for 

Compliance.

Unit has been reviewed and 

approved by Factory Mutual as a 

Temperature Limit Device per FM 

Class 3545 standard.  See: 

www.

fmglobal.com

Unit has been reviewed and 

approved by CSA International for 

use as Temperature Indicating-

Regulating Equipment per CSA 

C22.2 No. 24.  See: 

www.csa-

international.org

Warranty

This EZ-ZONE

®

 PM is manufactured by ISO 9001 regis-

tered processes and is backed by a three year warranty 

to the first purchaser for use, providing that the units 

have not been misapplied. Watlow's obligations here-

under, at Watlow's option, are limited to replacement, 

repair or refund of purchase price, and parts which 

upon examination prove to be defective within the war-

ranty period specified. This warranty does not apply 

to damage resulting from transportation, alteration, 

misuse or abuse. The purchaser must use Watlow parts 

to maintain all listed ratings.

Technical Assistance

You can get assistance from your local Watlow rep-

resentative (see back cover), send an email with your 

questions to: [email protected] or dial +1 

(507) 494-5656 between 7 a.m. and 5 p.m. Central 

Standard Time (CST) and ask for an Applications En-

gineer. Please have the following information available 

when calling:

• Complete model number 

• All configuration information

• User's Manual 

•  Factory Page

The EZ-ZONE PM Controller User’s Guide is copyrighted 

by Watlow Electric, Inc., © April 2013 with all rights 

reserved. The EZ-ZONE PM is covered by U.S. Patent 

No. 6,005,577 and Patents Pending

Product Overview

The EZ-ZONE PM Express single loop Limit controller is 

available in 1/4, 8

th

, 16

th

 or 32

nd

 DIN panel-mount pack-

ages. Ordering options include high or low voltage units 

with up to two outputs.

Installation and Wiring

Dimensions 1/16 DIN (PM6)

1/16 DIN (PM6) Recommended Panel Spacing

1/32 DIN (PM3) Recommended Panel Spacing

21.6 mm

(0.85 in)

minimum

21.6 mm

(0.85 in)

21.5 mm

(0.85 in)

21.6 mm

(0.85 in)

minimum

panel thickness 1.53 to 9.52 mm 

(0.060 to 0.375 in)

Side 

Front

Top 

Dimensions 1/32 DIN (PM3)

15.9 mm

(0.63 in)

101.6 mm

(4.00 in)

31.2 mm

(1.23 in)

53.3 mm

(2.10 in)

30.9 mm

(1.22 in)

Side 

Front 

Top 

15.8 mm

(0.62 in) 101.6 mm

(4.00 in)

51.2 mm

(2.02 in)

53.3 mm

(2.10 in)

53.3 mm

(2.10 in)

22.2 to 22.5 mm

(0.87 to 0.89 in)

44.96 to 45.47 mm

(1.77 to 1.79 in)

44.96 to 45.47 mm

(1.77 to 1.79 in)

44.96 to 45.47 mm

(1.77 to 1.79 in)

Summary of Contents for EZ-ZONE PM Express

Page 1: ...proved by Factory Mutual as a Temperature Limit Device per FM Class 3545 standard See www fmglobal com Unit has been reviewed and approved by CSA International for use as Temperature Indicating Regula...

Page 2: ...e blade of a screwdriver in the notch of the mounting collar assembly and push toward the panel while applying pressure to the face of the controller Don t be afraid to apply enough pressure to proper...

Page 3: ...ot con nect wires to unused terminals Note In the graphics below notice that the Slot A connector does not show labeling for the outputs Labeling for Slot A outputs is based on the controller part num...

Page 4: ...of outputs 1 and 2 Communications Activity Flashes when another device is communicating with this controller Upper Display On power up displays the process value otherwise displays the value of the p...

Page 5: ...Appears if Always tC Thermocouple MA Milliamps dc uolT Volts dc r0 1H RTD 100 Lin Lin Linearization Set the linearization to match the thermocouple type wired to this input For example select H for a...

Page 6: ...or Left Display Select parameter to display Appears if Always AC Pu Active Process Value none None loC Lockout Menu SEn Sensor Type Lin Linearization t C Thermistor Curve r r Resistance Range deC Deci...

Page 7: ...lpha Techniques Beta THERM YSI Prompt tC 2 252K Curve A 2 2K3A 004 A 10K Curve A 10K3A 016 B 10K Curve C 10K4A 006 C Functional Operating Range Type B 50 to 1816 C 58 to 3301 F Type C 0 to 2315 C 32 t...

Page 8: ...fo watlow co uk Website www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Pacific Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139...

Reviews: