Operations Menu
Display
Parameter Name Description
Range
Defaults are shown
bold
[`LL;S]
[ LL.S]
Limit Low Set Point
Set the low process value that will trigger the limit.
Appears if: Limit sides set to low or both.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C
[`Lh;S]
[ Lh.S]
Limit High Set Point
Set the high process value that will trigger the limit.
Appears if: Limit sides set to high or both.
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 0.0°F or -18.0°C
[`A;Lo]
[ A.Lo]
Alarm Low Set Point
Process - set the process value that will trigger a low
alarm.
Appears if: Alarm Type (A.ty) is set to Process Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 32.0°F or 0.0°C
[`A;hi]
[ A.hi]
Alarm High Set Point
Process - set the process value that will trigger a high
alarm.
Appears if: Alarm Type (A.ty) is set to Process Alarm
-1,999.000 to 9,999.000°F or units
-1,128.000 to 5,537.000°C
Units, 300.0°F or 150.0°C
[`i;CA]
[ i.CA]
Calibration Offset
Set an offset value for a process output.
Appears if: Always
-1,999.000 to 9,999.000°F or units
-1,110.555 to 5,555.000°C
0.0
‰
[````]
PAr1
[````]
PAr2
[`ll;s]
Limit Low Set Point
[`lh;s]
Limit
High Set Point
[`A;lo]
Alarm Low Point
[`A;hi]
Alarm High Point
[`i;Ca]
Calibration Offset
Operations Menu
Upon power up of the control,
using the advance key will scroll
through the various prompts found
in the Operations Menu. At any
point within the Operations menu
to return to the default display push
the Reset
key.
17 18
19 20
Setup Menu
Display
Parameter Name Description
Range (
Defaults are shown
bold)
LoC
[LoC]
Lockout Menu
Set the security clearance level. The user can access the selected level and
all lower levels.
Appears if: Always
1 to 5
1 Operations Menu (read only)*
2 Operations Menu (Set point R/W)*
3 Operations Menu (Set point R/W, Control Mode R/W)*
4 Operations Menu R/W access)*
5 Operations Menu and Setup Menu full R/W access
*You can change the security level at any level
[Sen]
[ SEn]
Sensor Type
Set the analog sensor type to match the device wired to this input.
Appears if: Always.
[``tC]
Thermocouple
[`MA]
Milliamps dc
[uolT]
Volts dc
[r0;1H]
RTD 100 Ω
[Lin]
[ Lin]
Linearization
Set the linearization to match the thermocouple type wired to this input.
For example, select
[```H]
for a type K thermocouple.
Appears if: Sensor Type is set to Thermocouple.
[`b]
B
[`J]
J
[`t]
T
[`c]
C
[`H]
K
[`d]
D
[`n]
N
[`e]
E
[`r]
R
[`f]
F
[`S]
S
[``t;C]
[ t.C]
Thermistor Curve
Select a curve to apply to the thermistor input.
[```A]
Curve A,
[```b]
Curve B,
[```C]
Curve C
[CUSt]
Custom
[``r;r]
[ r.r]
Resistance Range
Set the maximum resistance of the thermistor input.
[```5]
5K,
[``10]
10K,
[``20]
20K,
[``40]
40K
[`dEC]
[ dEC]
Decimal
Set the precision of the displayed value.
Appears if: Always.
[```0]
Whole
[``0;0]
Tenths
[`0;00]
Hundredths
[`C_F]
[ C_F]
Display Units
Select which units will be displayed.
Appears if: Always.
[```F]
°F
[```C]
°C
[`r;Lo]
[ r.Lo]
Limit Set Point - Range Low
Sets the low limit of the set point adjustment using a T/C and RTD; scales for
process inputs.
Appears if: Always.
-1,999.00 to 9,999.000 °F or Units
-1,110.555 to 5,555.000 °C
0.0
[`r;hi]
[ r.hi]
Limit Set Point - Range High
Sets the high limit of the set point adjustment using a T/C and RTD; scales for
process inputs.
Appears if: Always.
-1,999.00 to
9,999.000
°F or Units
-1,110.555 to 5,555.000 °C
[`fn1]
[ fn1]
Function of Output 1
Select which function will drive this output.
Appears if: Always.
[`oFF]
Off,
[LiM]
Limit*,
[ALM]
Alarm
*Note:
Switched DC/Open Collector option should only be used to control an
external mechanical relay if Limit function is selected.
‰
[`loC]
Lockout Menu
[`SEn]
Sensor Type
[`Lin]
Linearization
[``t;C]
Thermistor Curve
[``r;r]
Resistance Range
[`deC]
Decimal
[`C_F]
Display Units
[`r;lo]
Limit Set Point Range Low
[`r;hi]
Limit Set Point Range High
[`fn1]
Function Output One
[`fn2]
Function Output Two
[`l;sd]
Limit Sides
[`l;hy]
Limit Hysteresis
[`A;ty]
Alarm Type
[`A;hy]
Alarm Hysteresis
[`A;lg]
Alarm Logic
[`A;lA]
Alarm Latching
[`A;bl]
Alarm Blocking
[`A;si]
Alarm Silencing
[A;dsp]
Alarm Display
[par1]
Upper or Left Display
[par2]
Lower or Right Display
[`Ad;s]
Zone Address
Setup Menu
To enter the Setup Menu push and hold
the up and down arrow keys for ap-
proximately 3 seconds. Once there, push
the green advance key to scroll through
to the prompt of choice and then use
the up and down arrow keys to change
the range. At any point within the Setup
menu to return to the default display
push the Reset
key.