Setup Menu

Display

Parameter Name Description

Range (

Defaults are shown 

bold)

[`fn2]

[ fn2]

Function of Output 2

Select which function will drive this output.

Appears if: Always.

[`LiM]

 

Limit

Note:

Output 2 (only) is FM approved as a limit.

 

[`L;Sd]

[ L.Sd]

Limit Sides

Select which side or sides of the process value will be monitored.

Appears if: Always.

[both]

 

Both

[high] 

High

[LoW]

 Low

[`L;hy]

[ L.hy]

Limit Hysteresis

Set the hysteresis for the limit function. This determines how far into the safe 

range the process value must move before the limit turns the output back on.

Appears if: Always.

0.001 to 9,999.0°F or units
0.001 to 5,555.0°C

Units, 3.0°F or 2°C

[`A;ty]

[ A.ty]

Alarm Type

Select how the alarm will or will not track the set point.

Appears if: Always.

[`oFF]

 

Off

 

[PR;AL]

 Process Alarm  

[`A;hy] 

[ A.hy]

Alarm Hysteresis 

Set the hysteresis for an alarm. This determines how far into the safe region the 

process value needs to move before the alarm can be cleared.

Appears if: When alarm type is set to process.

0.001 to 9,999.000°F or units
0.001 to 5,555.000°C

Units, 1.0°F or 1.0°C

[a;lg]

[A.Lg]

Alarm Logic

Select what the output condition will be during the alarm state.

Appears if: Always

[

`a;lC] 

Close on Alarm

 

[`a;lo] 

Open on alarm

[

`A;LA] 

[ A.LA]

Alarm Latching

Turn alarm latching on or off. A latched alarm has to be turned off by the user.

Appears if: When alarm type is set to process.

[

nLAt] 

Non-Latching 

[`LAt] 

Latching

`A;bL]

[ A.bL]

Alarm Blocking

Select when an alarm will be blocked. After startup and/or after the set point 

changes, the alarm will be blocked until the process value enters the normal 

range.

Appears if: When alarm type is set to process.

[`oFF]

 Off 

[`Str]

 Startup 

[StPt]

 Set Point 

[both]

 Both 

[`A;si]

[ A.Si]

Alarm Silencing

Turn alarm silencing on to allow the user to disable the output tied (configured) 

to this alarm

Appears if: Always.

[`oFF]

 

Off 

[``on]

 On

[A;dSP]

[A.dSP]

Alarm Display

Display an alarm message when an alarm is active.

Appears if: When alarm type is set to process.

[`oFF]

 Off 

[``on]

 

On

[PAr1] 

[PAr1]

Upper or Left Display

Select parameter to display.

Appears if: Always.

[AC;Pu] 

Active Process Value

[none] 

None 

[`loC]

 Lockout Menu

[`SEn]

 Sensor Type

[`Lin]

 Linearization

[``t;C]

 Thermistor Curve

[``r;r]

 Resistance Range

[`deC]

 Decimal

[`C_F]

 Display Units

[`r;lo]

 Limit Set Point Range Low

[`r;hi]

 Limit Set Point Range High

[`fn1]

 Function Output One

[`fn2]

 Function Output Two

[`l;sd]

 Limit Sides

[`l;hy]

 Limit Hysteresis

[`A;ty]

 Alarm Type

[`A;hy]

 Alarm Hysteresis

[`A;lg]

 Alarm Logic

[`A;lA]

 Alarm Latching

[`A;bl]

 Alarm Blocking

[`A;si]

 Alarm Silencing

[A;dsp]

 Alarm Display

[par1]

 Upper or Left Display

[par2]

 Lower or Right Display

[`Ad;s]

 Zone Address

Setup Menu

To enter the Setup Menu push and hold 

the up and down arrow keys for ap-

proximately 3 seconds. Once there, push 

the green advance key to scroll through 

to the prompt of choice  and then use the 

up and down arrow keys to change the 

range. At any point within the Operations 

menu to return to the default display 

push the Reset 

key.

21 22
23 24

[`loC]

 Lockout Menu

[`SEn]

 Sensor Type

[`Lin]

 Linearization

[``t;C]

 Thermistor Curve

[``r;r]

 Resistance Range

[`deC]

 Decimal

[`C_F]

 Display Units

[`r;lo]

 Limit Set Point Range low

[`r;hi]

 Limit Set Point Range High

[`fn1]

 Function Output One

[`fn2]

 Function Output Two

[`l;sd]

 Limit Sides

[`l;hy]

 Limit Hysteresis

[`A;ty]

 Alarm Type

[`A;hy]

 Alarm Hysteresis

[`A;lg]

 Alarm Logic

[`A;lA]

 Alarm Latching

[`A;bl]

 Alarm Blocking

[`A;si]

 Alarm Silencing

[A;dsp]

 Alarm Display

[par1]

 Upper or Left Display

[par2]

 Lower or Right Display

[`Ad;s]

 Zone Address

Setup Menu

To enter the Setup Menu push and hold 

the up and down arrow keys for ap-

proximately 3 seconds. Once there, push 

the green advance key to scroll through 

to the prompt of choice  and then use the 

up and down arrow keys to change the 

range. At any point within the Operations 

menu to return to the default display 

push the Reset 

key.

Setup Menu

Display

Parameter Name Description

Range (

Defaults are shown 

bold)

[PAr2] 

[PAr2]

Lower or Right Display

Select parameter to display.

Appears if: Always.

[`Ls;t] 

Limit State 

[`A;hi] 

Alarm High Set Point

[`Lh;S] 

Limit High Set Point 

[`A;lo] 

Alarm Low Set Point

[`LL;S] 

Limit Low Set Point 

[none] 

None 

[`ad;s] 

[ Ad.S]

Zone Address - Standard Bus Communication

Set zone address from 1-16.

Appears if: Always.

1-16

1

  

Summary of Contents for EZ-ZONE PM Express

Page 1: ...proved by Factory Mutual as a Temperature Limit Device per FM Class 3545 standard See www fmglobal com Unit has been reviewed and approved by CSA International for use as Temperature Indicating Regula...

Page 2: ...e blade of a screwdriver in the notch of the mounting collar assembly and push toward the panel while applying pressure to the face of the controller Don t be afraid to apply enough pressure to proper...

Page 3: ...ot con nect wires to unused terminals Note In the graphics below notice that the Slot A connector does not show labeling for the outputs Labeling for Slot A outputs is based on the controller part num...

Page 4: ...of outputs 1 and 2 Communications Activity Flashes when another device is communicating with this controller Upper Display On power up displays the process value otherwise displays the value of the p...

Page 5: ...Appears if Always tC Thermocouple MA Milliamps dc uolT Volts dc r0 1H RTD 100 Lin Lin Linearization Set the linearization to match the thermocouple type wired to this input For example select H for a...

Page 6: ...or Left Display Select parameter to display Appears if Always AC Pu Active Process Value none None loC Lockout Menu SEn Sensor Type Lin Linearization t C Thermistor Curve r r Resistance Range deC Deci...

Page 7: ...lpha Techniques Beta THERM YSI Prompt tC 2 252K Curve A 2 2K3A 004 A 10K Curve A 10K3A 016 B 10K Curve C 10K4A 006 C Functional Operating Range Type B 50 to 1816 C 58 to 3301 F Type C 0 to 2315 C 32 t...

Page 8: ...fo watlow co uk Website www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Pacific Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139...

Reviews: