Setup Menu
Display
Parameter Name Description
Range (
Defaults are shown
bold)
[`fn2]
[ fn2]
Function of Output 2
Select which function will drive this output.
Appears if: Always.
[`LiM]
Limit
Note:
Output 2 (only) is FM approved as a limit.
[`L;Sd]
[ L.Sd]
Limit Sides
Select which side or sides of the process value will be monitored.
Appears if: Always.
[both]
Both
[high]
High
[LoW]
Low
[`L;hy]
[ L.hy]
Limit Hysteresis
Set the hysteresis for the limit function. This determines how far into the safe
range the process value must move before the limit turns the output back on.
Appears if: Always.
0.001 to 9,999.0°F or units
0.001 to 5,555.0°C
Units, 3.0°F or 2°C
[`A;ty]
[ A.ty]
Alarm Type
Select how the alarm will or will not track the set point.
Appears if: Always.
[`oFF]
Off
[PR;AL]
Process Alarm
[`A;hy]
[ A.hy]
Alarm Hysteresis
Set the hysteresis for an alarm. This determines how far into the safe region the
process value needs to move before the alarm can be cleared.
Appears if: When alarm type is set to process.
0.001 to 9,999.000°F or units
0.001 to 5,555.000°C
Units, 1.0°F or 1.0°C
[a;lg]
[A.Lg]
Alarm Logic
Select what the output condition will be during the alarm state.
Appears if: Always
[
`a;lC]
Close on Alarm
[`a;lo]
Open on alarm
[
`A;LA]
[ A.LA]
Alarm Latching
Turn alarm latching on or off. A latched alarm has to be turned off by the user.
Appears if: When alarm type is set to process.
[
nLAt]
Non-Latching
[`LAt]
Latching
`A;bL]
[ A.bL]
Alarm Blocking
Select when an alarm will be blocked. After startup and/or after the set point
changes, the alarm will be blocked until the process value enters the normal
range.
Appears if: When alarm type is set to process.
[`oFF]
Off
[`Str]
Startup
[StPt]
Set Point
[both]
Both
[`A;si]
[ A.Si]
Alarm Silencing
Turn alarm silencing on to allow the user to disable the output tied (configured)
to this alarm
Appears if: Always.
[`oFF]
Off
[``on]
On
[A;dSP]
[A.dSP]
Alarm Display
Display an alarm message when an alarm is active.
Appears if: When alarm type is set to process.
[`oFF]
Off
[``on]
On
[PAr1]
[PAr1]
Upper or Left Display
Select parameter to display.
Appears if: Always.
[AC;Pu]
Active Process Value
[none]
None
‰
[`loC]
Lockout Menu
[`SEn]
Sensor Type
[`Lin]
Linearization
[``t;C]
Thermistor Curve
[``r;r]
Resistance Range
[`deC]
Decimal
[`C_F]
Display Units
[`r;lo]
Limit Set Point Range Low
[`r;hi]
Limit Set Point Range High
[`fn1]
Function Output One
[`fn2]
Function Output Two
[`l;sd]
Limit Sides
[`l;hy]
Limit Hysteresis
[`A;ty]
Alarm Type
[`A;hy]
Alarm Hysteresis
[`A;lg]
Alarm Logic
[`A;lA]
Alarm Latching
[`A;bl]
Alarm Blocking
[`A;si]
Alarm Silencing
[A;dsp]
Alarm Display
[par1]
Upper or Left Display
[par2]
Lower or Right Display
[`Ad;s]
Zone Address
Setup Menu
To enter the Setup Menu push and hold
the up and down arrow keys for ap-
proximately 3 seconds. Once there, push
the green advance key to scroll through
to the prompt of choice and then use the
up and down arrow keys to change the
range. At any point within the Operations
menu to return to the default display
push the Reset
key.
21 22
23 24
‰
[`loC]
Lockout Menu
[`SEn]
Sensor Type
[`Lin]
Linearization
[``t;C]
Thermistor Curve
[``r;r]
Resistance Range
[`deC]
Decimal
[`C_F]
Display Units
[`r;lo]
Limit Set Point Range low
[`r;hi]
Limit Set Point Range High
[`fn1]
Function Output One
[`fn2]
Function Output Two
[`l;sd]
Limit Sides
[`l;hy]
Limit Hysteresis
[`A;ty]
Alarm Type
[`A;hy]
Alarm Hysteresis
[`A;lg]
Alarm Logic
[`A;lA]
Alarm Latching
[`A;bl]
Alarm Blocking
[`A;si]
Alarm Silencing
[A;dsp]
Alarm Display
[par1]
Upper or Left Display
[par2]
Lower or Right Display
[`Ad;s]
Zone Address
Setup Menu
To enter the Setup Menu push and hold
the up and down arrow keys for ap-
proximately 3 seconds. Once there, push
the green advance key to scroll through
to the prompt of choice and then use the
up and down arrow keys to change the
range. At any point within the Operations
menu to return to the default display
push the Reset
key.
Setup Menu
Display
Parameter Name Description
Range (
Defaults are shown
bold)
[PAr2]
[PAr2]
Lower or Right Display
Select parameter to display.
Appears if: Always.
[`Ls;t]
Limit State
[`A;hi]
Alarm High Set Point
[`Lh;S]
Limit High Set Point
[`A;lo]
Alarm Low Set Point
[`LL;S]
Limit Low Set Point
[none]
None
[`ad;s]
[ Ad.S]
Zone Address - Standard Bus Communication
Set zone address from 1-16.
Appears if: Always.
1-16
1