Specifications

Line Voltage/Power

•  All voltage levels represent minimums and maximums

•  85 to 264V~(ac), 47 to 63Hz

•  20 to 28V

Å

(ac), +10/-15 percent; 50/60Hz, ±5 percent

•  12 to 40V

Î

(dc)

•  10VA maximum power consumption (PM3 and PM6) 
•  14VA maximum power consumption (PM4, 8 and 9)

 

 

•  Data retention upon power failure via nonvolatile memory

•  Compliant with SEMI F47-0200, Figure R1-1 voltage sag requirements @ 24V

Å

(ac) or higher 

Environment

•  -18 to 65°C (0 to 149°F) operating temperature

•  -40 to 85°C (-40 to 185°F) storage temperature

•  0 to 90 percent RH, non-condensing

Accuracy

•   Calibration accuracy and sensor conformity: ±0.1 percent  of span, ±1°C @ the calibrated ambient tempera

-

ture and rated line voltage

•  Type S, 0.2 percent

•  Type T, below -50°C; 0.2 percent

•   Calibration ambient temperature @ 25°C ±3°C (77°F ±5°F)

•   Accuracy span: 540°C (1000°F) minimum

•   Temperature stability: ±0.1°C/°C (±0.1°F/°F) rise in ambient maximum

Agency Approvals

•   cULus

®

 UL/EN/CSA C22.2 No. 61010-1 Listed File E185611

•   cULus

®

 ANSI/ISA 12.12.01-2007, CSA-C22.2 No.213-1987, Class 1 Division 2 Groups A, B, C and D, 

Temperature Code T4A, File E184390 (optional)

•   UL

®

 50, 4X indoor locations, NEMA 4X, IP66 front seal

•   CSA C22.2 No. 24 File 158031 (1/32 and 1/16 DIN sizes)

•   CE, RoHS by design, W.E.E.E.  

•   FM Class 3545 File 3029084

•   SEMI F47-0200

Serial Communications

•   Isolated communications 

•  Standard Bus Configuration Protocol

Wiring Termination—Touch-Safe Terminals

•  Input, power and controller output terminals are touch safe removable 12 to 22 AWG 

•  Use 75°C, Cu conductor only

Universal Input

•  Thermocouple, grounded or ungrounded sensors

•   >20MΩinput impedance

•  Maximum of 2KΩ source resistance (applies to T/C only)

•  RTD 2- or 3-wire, platinum, 100Ω @ 0°C calibration to DIN curve (0.00385 Ω/Ω/°C)

•   Process, 4-20mA @ 100Ω, or 0-10V

Î

(dc) @ 20kΩ input impedance; scalable 

Thermistor Input (

Not included with Universal Input

)

Thermistor Input

Input Type

Max Error 

@ 25 Deg C

Accuracy 

Range Low

Accuracy 

Range High

Units

Thermistor, 5K range

±5

0

5000

Ohms

Thermistor, 10K range

±10

0

10000

Ohms

Thermistor, 20K range

±20

0

20000

Ohms

Ordering Part Number

 

(Part number digits 1 through 14)

 PMXLXXX-AAAABXX

All Models include: *Universal Sensor Input, Standard Bus Configuration Communications 

*Dual line Red over Green 7 Segment displays

Package Size

 (

Digit #3

)

3 = 1/32 DIN

6 = 1/16 DIN

8 = 1/8 DIN vertical

9 = 1/8 DIN horizontal 

4 = 1/4 DIN

Primary Function 

 (

Digit #4

)

L = Limit Controller w/ Universal Input

Power Supply

 (

Digit #5

)

1 = 100-240 VAC

3 = 12-28 VAC/DC

Output 1 and 2 Hardware Options

 (

Digits #6 and #7

)

 

Output 1 

Output 2

AJ = None 

Mechanical relay 5A, Form A

CJ  = Switched dc/open collector 

Mechanical relay 5A, Form A

EJ  = Mechanical Relay 5 Amp form C 

Mechanical relay 5A, Form A

Future Options

 (

Digits #8 thru #11

)

AAAA = None

Menu Type

 (

Digits #12

)

B  = Express

Additional Options

 (

Digits #13 and #14

)

AA =  Standard EZ-ZONE face plate
AB =  EZ-ZONE logo and no Watlow name
AC =  No logo and no Watlow name

Thermistor Input 

(cont.)

Thermistor, 40K range

±40

0

40000

Ohms

•  0 to 40KΩ, 0 to 20KΩ, 0 to 10KΩ, 0 to 5KΩ
•  2.252KΩ and 10KΩ base at 77°F (25°C)
•  Linearization curves built in
•  Third party Thermistor compatibility requirements

Base R @ 

25C

Alpha 

Techniques

Beta THERM

YSI

Prompt

[``tC]

2.252K

Curve A

2.2K3A

004

A

10K

Curve A

10K3A

016

B

10K

Curve C

10K4A

006

C

Functional Operating Range

•  Type B: -50 to 1816°C (-58 to 3301°F)

•  Type C: 0 to 2315°C (32 to 4199°F)

•  Type D: 0 to 2315°C (-328 to 4199°F)

•  Type E: -270 to 1000°C (-454 to 1832°F)

•  Type F: 0 to 1343°C (32 to 2449°F)

•  Type J: -210 to 1200°C (-346 to 

2192

°F)

•  Type K: -270 to 1371°C (-454 to 2500°F)

•  Type N: -200 to 1300°C (-328 to 2372°F)

•  Type R: -50 to 1767°C (-58 to 3213°F)

•  Type S: -50 to 1767°C (-58 to 3213°F)

•  Type T: -270 to 400°C (-454 to 752°F)

•  RTD (DIN): -200 to 800°C (-328 to 1472°F)

• 

Process: -1999 to 9999 units

Output Hardware

•  Switched dc 

- 22 to 32V

Î

(dc) @ 30mA

•  Open collector, maximum sink current 100 mA, @ 30V

Î

(dc) 

•   Electromechanical relay, Form C, 5A, 24 to 240V

Å

(ac) or 30V

Î

(dc) maximum, resistive load, 100,000 

cycles at rated load

•  Electromechanical relay, Form A, 5A, 24 to 240V

Å

(ac) or 30V

Î

(dc) maximum, resistive load, 100,000 

cycles at rated load

Operator Interface

•  Dual 4 digit, 7 segment LED displays

•  Typical display update rate 1Hz

•  Advance, RESET, up and down keys plus an EZ-Key/s (not available in 1/32 DIN)

Declaration of Conformity 

CE DOC EZ-ZONE PM-06-09 

Series EZ-ZONE

®

 PM 

WATLOW 

      

 

 

an

ISO 9001

 approved facility since 1996. 

1241 Bundy Blvd.  

Winona, MN 55987 USA 

Declares that the following product: 
Designation: 

Series EZ-ZONE

®

 PM (Panel Mount) 

Model Numbers: 

PM (3, 6, 8, 9 or 4)(Any Letter or number) – (1, 2, 3 or 4)(A, C, E, F or 

K) (A, C, H, J or K)(Any letter or number) – (Any letter or number)(A, C, 

E, F or K)(A, C, H, J or K) (Any three letters or numbers) 

Classification: 

Temperature control, Installation Category II, Pollution degree 2, IP66 

Rated Voltage and Frequency:  100 to 240 V~ (ac 50/60 Hz) 

or

 15 to 36 V

dc/ 24 V~ac 50/60 Hz 

Rated Power Consumption: 

10 VA maximum PM3, PM6 Models. 

14 VA maximum PM8, PM9, PM4 Models 

Meets the essential requirements of the following European Union Directives by using the relevant 

standards show below to indicate compliance. 

2004/108/EC Electromagnetic Compatibility Directive 

EN 61326-1 

2006 

Electrical equipment for measurement, control and laboratory 

use – EMC requirements (Industrial Immunity, Class B 

Emissions).

EN 61000-4-2 

1996 +A1,A2 

Electrostatic Discharge Immunity 

EN 61000-4-3 

2006 

Radiated Field Immunity 10V/M 80–1000 MHz, 3 V/M 1.4–2.7 GHz 

EN 61000-4-4 

2004 

Electrical Fast-Transient / Burst Immunity 

EN 61000-4-5 

2006 

Surge Immunity 

EN 61000-4-6 

1996 +A1,A2,A3  Conducted Immunity 

EN 61000-4-11  2004 

Voltage Dips, Short Interruptions and Voltage Variations Immunity 

EN 61000-3-2 

2006 

Harmonic Current Emissions 

EN 61000-3-3

1

2005 

Voltage Fluctuations and Flicker 

SEMI F47 

2000 

Specification for Semiconductor Sag Immunity Figure R1-1 

1

For mechanical relay loads, cycle time may need to be extended up to 160 seconds to meet flicker 

requirements depending on load switched and source impedance. 

2006/95/EC Low-Voltage Directive 

EN 61010-1 

2001 

Safety Requirements of electrical equipment for measurement, 

control and laboratory use. Part 1: General requirements 

Compliant with 2002/95/EC RoHS Directive 

Per 2002/96/EC W.E.E.E Directive 

 Please Recycle Properly. 

Raymond D. Feller III  

 

Winona, Minnesota, USA 

Name of Authorized Representative   

Place of Issue 

General Manager 

 

June 2009 

Title of Authorized Representative 

 

Date of Issue 

Signature of Authorized Representative 

Specifications (

cont.

)

Summary of Contents for EZ-ZONE PM Express

Page 1: ...proved by Factory Mutual as a Temperature Limit Device per FM Class 3545 standard See www fmglobal com Unit has been reviewed and approved by CSA International for use as Temperature Indicating Regula...

Page 2: ...e blade of a screwdriver in the notch of the mounting collar assembly and push toward the panel while applying pressure to the face of the controller Don t be afraid to apply enough pressure to proper...

Page 3: ...ot con nect wires to unused terminals Note In the graphics below notice that the Slot A connector does not show labeling for the outputs Labeling for Slot A outputs is based on the controller part num...

Page 4: ...of outputs 1 and 2 Communications Activity Flashes when another device is communicating with this controller Upper Display On power up displays the process value otherwise displays the value of the p...

Page 5: ...Appears if Always tC Thermocouple MA Milliamps dc uolT Volts dc r0 1H RTD 100 Lin Lin Linearization Set the linearization to match the thermocouple type wired to this input For example select H for a...

Page 6: ...or Left Display Select parameter to display Appears if Always AC Pu Active Process Value none None loC Lockout Menu SEn Sensor Type Lin Linearization t C Thermistor Curve r r Resistance Range deC Deci...

Page 7: ...lpha Techniques Beta THERM YSI Prompt tC 2 252K Curve A 2 2K3A 004 A 10K Curve A 10K3A 016 B 10K Curve C 10K4A 006 C Functional Operating Range Type B 50 to 1816 C 58 to 3301 F Type C 0 to 2315 C 32 t...

Page 8: ...fo watlow co uk Website www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Pacific Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139...

Reviews: