background image

12

FLUSHING, CONDITIONING AND SANITIZATION

Step 1.

  Make sure the system is in the “Bypass” position before turning the main water back on (

see figure 12a above

).

 

Make sure the drain line is connected securely to the control valve and is properly located over a drain.

 

Make sure the drain line is connected to the overflow elbow 

(see figure 6, page 7)

 and is properly located over a drain. 

 

Make sure the brine line is connected to both the air check in the brine well and the control valve. (

see figure 7, page 7

)

  

Make sure the control valve is plugged into an operating outlet with the correct voltage and is properly grounded.

Step 2: 

  Press and Hold the REGEN button on the Triton until you hear the motor engage. This will initiate an immediate manual regeneration 

of the system. Refer to the table on page 10 for Triton cycles of operation.  Turn the bypass valve to Normal Operation (

figure 12b 

above

) (you should hear water entering the system.)  Wait a few minutes to ensure the control valve can draw water and does not 

leak. If everything is working, press and release the REGEN button. You will hear the motor engage and move the piston into the 

“Brine Dn” position. Check the brine line for leaks or suction. You should hear the valve drawing brine.  Continue to skip cycles by 

pressing and releasing the REGEN button (wait for the motor to stop before pressing REGEN)  until you reach the “Brine Fill” position. 

This ensures that water will go to the brine tank.  Fill tank 3” to 4” above salt grid. Make sure enough water is in the brine tank to 

dissolve the correct amount of salt for regeneration (1 gallon of water will dissolve 3 lbs. of sodium chloride). Allow the brine tank to 

fill with water to air check level. If the system needs 6 lbs. of salt to regenerate, then at least 2-1/2 gallons of water must be in the 

brine tank above air check in the brine well. The extra 1/2 gallon is an additional measure for evaporation or loss. (6 ÷ 3 = 2 gallons of 

water plus 1/2 gallon). Fill the brine tank with salt. (We recommend potassium chloride (KCl) instead of rock salt.) Once the brine tank 

is filled  to this level, press REGEN once more to return the valve to service. You should hear the motor engage for a short period and 

then a long period.

Figure 12a.

Bypass Operation

Figure 12b.

Normal Operation

Did you connect the drain line securely to the
Triton’s drain elbow?

Did you connect the brine line securely to the
Triton’s brine elbow?

Starting Up The System

STOP

Summary of Contents for REIONATOR PRO ULTRA RXU13

Page 1: ...NER with Triton Electronic Control Valve INSTALLATION AND SERVICE MANUAL IAPMO R T certified to NSF ANSI Standards 42 and 44 for meeting or exceeding industry standards of aesthetic chlorine reduction...

Page 2: ...ness by gallons per day of people times 75 gallons person day For example there are 4 people in a home and you are installing a 32 000 grain Reionator Pro Ultra which has an optimum capacity of 16 080...

Page 3: ...rain and direct sunlight IMPORTANT Damage to the Reionator Pro Ultra as a result of exposure to the elements without the use of a weather cover will not be covered under the limited lifetime warranty...

Page 4: ...NECTION Install 1 2 I D plastic tubing from the hose barb located on the right side of the main control valve to an open drain Do not connect the drain directly to a sewer as this would violate sanita...

Page 5: ...nimum run between Reionator Pro unit and water heater hot cold hot water heater typical plumbing installation Triton Bypass Valve Important Brass or Plastic yoke assembly not shown is required to conn...

Page 6: ...ll 1 2 I D tubing not provided to the brine tank overflow fitting located on the side of the tank and run it to the drain The brine overflow is provided in case a situation should arise causing too mu...

Page 7: ...e tank Position mark on air check valve at same level as surface of salt grating to floor drain salt grating air check valve positioning mark brine well cap to aircheck overflow elbow brine well Figur...

Page 8: ...nd release the Set Time button The screen should change to the Set Time screen and the hour should flash Press and release either the or buttons until the desired hour of the day is reached AM or PM w...

Page 9: ...rs should stop flashing and the minutes should begin flashing Press either the or buttons to change the minutes as shown in Figure 9b When you ve finished setting the time press and release the Set Ti...

Page 10: ...e bypass has straight fittings The Triton uses no traditional fasteners e g screws instead clips threaded caps and nuts and snap type latches are used Caps and nuts only need to be firmly hand tighten...

Page 11: ...11 Bypass Valve Operation...

Page 12: ...e piston into the Brine Dn position Check the brine line for leaks or suction You should hear the valve drawing brine Continue to skip cycles by pressing and releasing the REGEN button wait for the mo...

Page 13: ...rn to service In step 5 you will set the valve to Regen Today so that it will regen tonight at the specified time If there is any residual chlorine it should be removed tonight Step 4 Make sure that t...

Page 14: ...a comes pre set from the factory to perform as a typical softener valve However there are certain settings that are specific to the customer s water situation that cannot be set at the factory This se...

Page 15: ...rom the Set HARDNESS screen press the NEXT button You should now see the Set REGEN DAY screen shown above Simply press the or button to change the day override IMPORTANT This screen is used to set the...

Page 16: ...ne flow control if plugged E Hot water tank hardness E Repeated flushings of the hot water tank is required F Leak at distributor tube F Make sure distributor tube is not cracked and check O ring and...

Page 17: ...oreign material and check control in various regeneration positions B Internal control leak B Replace seals and or piston assembly C Control valve jammed in brine or C Replace seals and or piston back...

Page 18: ...SAFE OR OF UNKNOWN QUALITY WITHOUT ADEQUATE DISINFECTION BEFORE AND OR AFTER THE SYSTEM USAGE OF THE REIONATOR PRO ULTRA IN A MANNER OTHER THAN PRESCRIBED IN THE MANUFACTURER S WARRANTY WILL VOID THE...

Page 19: ...PTION PART NUMBER Resin Tank 13 x 54 09 03 1354BLK Xmid Brine Tank 09 04 1833BKC Brine Grid 18 09 04 119 Brine Well Assembly 3 5 X 30 09 04 240 Brine Overflow Elbow 07 05 004 Triton Control Valve 13 V...

Page 20: ...06 01 020 10 03 2017 800 FREEPORT PARKWAY 150 COPPELL TX 75019 888 254 8412 www watertech com...

Reviews: