Calibrating the System—Auto Mode
2
3
4
Use the illustrations and instructions to adjust the
system in auto mode.
When operating the system:
•
Always start the system in auto or unload mode.
•
Always circulate enough cool water to regulate
the compressor oil temperature during operation.
•
Never operate the system with the compressor oil
temperature above 250°F (121°C).
1 Use caution when performing this procedure.
• Rotating parts can cause
severe injury or death.
Moving Parts
• Do not enter or reach into
the compartment when
equipment is operating.
2 Make sure that the pump has 100 psi (10.3 bar)
at the main discharge with minimal flow.
3 Toggle the auto-sync switch to the
Auto
position.
4 Make sure that the air pressure is equal to, or
up to 5% higher than, the static water pressure.
Raise and lower the static water pressure to
make sure that the air pressure follows the
static water pressure.