35
|
107
Safety
Introduction
Product Overview
Installation
Operation
Troubleshooting
Maintenance
Auto-Sync Mode Switch
Feature
Feature
Description
Description
1 Power wire
This connects to apparatus power.
2 Wire harness connector
This connects to the wire harness on the auto-sync assembly.
3 Mounting hole
This secures the plate to the apparatus.
4 Unload mode
This mode operates the compressor at approximately 40 psi (2.8 bar).
The compressor generates a minimum pressure of 40
psi (2.8 bar) to circulate the compressor oil and cool the system. Always start the compressor in this mode or auto mode.
5 Auto mode
This mode operates the compressor at 50 to 150 psi (3.4 to 10.3 bar). The system automatically adjusts the air pressure as you
raise and lower the water pressure. Always start the compressor in this mode or unload mode.
6 Fixed mode
This mode operates the compressor at 150 psi (10.3 bar) regardless of water pressure.
7 3-way switch
This toggles between the 3 operation modes.