Installing the Oil Sump
1
2
3
4
7
Use the illustrations and instructions to install the oil
sump.
Note:
Make sure to install the sump so that it is
easy to access. You must be able to perform
regular maintenance and see into the sight
window.
1 Install the sump with the oil drain toward the
bottom to facilitate drainage.
2 Install the oil sump so that the sight window is
below the top of the compressor.
3 Install the sump so that the sight window is
clearly visible.
4 Make sure that the sight window is visible.
Note:
If the sight window is not visible,
premature damage can occur and will
void your warranty.
5 Drill the mounting holes for the sump. Refer to:
"Dimensions—Sump, 8-Inch Long Version"
on page 40.
6 Use locally sourced hardware to secure the
sump to the apparatus.
Note:
Make sure to use the correct mounting
holes on the mounting plate.
7 Install the temperature sender.
Note:
The threads of the temperature sender
are the ground connection for the sensor.
Do not use thread tape on the threads.
There must be continuity between the
temperature sender and frame ground to
complete installation.
5
6