INSTALLATION & USER MANUAL
16
Installation and User Manual
17
Revision 8.12.2015
REMOTE DISPLAY
TROUBLESHOOTING TIPS
1. If in
AUTO
mode and operator(s) is not working as expected, make sure none of the secondary remotes are set to
AUTO
mode
and that temperature control (
TC)
for all zones on secondary remotes are set to
NULL
.
2.
MAX-OPEN
can be set to different values on both the main and secondary remotes. The operator will open to the
MAX-OPEN
setting of the remote used to open it. If the operator is not opening the proper amount be sure to check that
MAX-OPEN
is set
properly on the remote used.
3. Temperature control (
TC
) may also have to be set to have a lower
MAX-OPEN
value than the otherwise set
MAX-OPEN
.
4. Temperature change must be maintained for 10 minutes before the temperature control (
TC
) function will operate.
For more Trouble Shooting Tips, please visit www.SolarSmartOpener.com
ADVANCED SERVICE OPERATIONS
RESET OF REMOTE TO FACTORY SETTINGS
1. Press any key to wake up the remote, if the display has powered off.
2. Press and hold
MODE
, release when
PAIR
SET
is displayed.
3. Press
MODE
again to display
RE-ZONE
.
4. Press
MODE to
display
M
in the upper-right corner as flashing.
5. Press
ENTER
FAIL
is displayed as flashing.
6. Press and hold
MODE
, release when
rF TEST
is displayed.
7. Press
MODE
repeatedly until
rET FAC
is displayed.
8.
Press
ENTER
, all the screen display segments will be visible while the remote runs a self-test which lasts for a few seconds.
After which,
SET
will be displayed.
The remote has now been reset to factory settings; it is no longer paired to any operators.