TRACING FAULTS CHARTS (A/B ONLY)

 

 

 

21

18. Tracing faults 

 

Red LED 

Green LED 

  

Glo

w

in

per
ma
ne

ntl

Fl

as

hi

ng

 q

uic

kly

 

Fl

as

hi

ng

 slowly

 

Off
 

Glo

w

in

per
ma
ne

ntl

Fl

as

hi

ng

 q

uic

kly

 

Fl

as

hi

ng

 slowly

 

Off
 

  

  

  

  

  

  

  

  

  

Status 

Probable reasons 

Possible remedy 

  

  

  

  

  

  

x  Actuator does not respond, both 

LEDs are off 

1) No supply voltage applied 

2) The applied voltage does 

not match the actuator 

voltage on the tag plate 

1) Check mains supply 

2) Apply correct supply 

voltage 

  

  

  

  

  

   Actuator does not drive the full 

stroke 

1) Actuator not correctly 

commissioned 

2) Too small stroke 

programmed (in mode “one 

position‐dependent cut‐

off”) 

1) Repeat commissioning 

2) Check valve stroke 

parameters ‐> see 

instructions AMS‐PSCS 

  

  

  

  

  

   Actuator does not close the valve 

properly  

1) Actuator  not correctly 

commissioned  

2) Actuator closing force/ 

torque too low 

1) Repeat commissioning 

2) Check actuator selection 

  

  

  

  

  

   Actuator is in normal operating 

condition, but does not respond to 

set‐value changes 

1) Fixed digital set‐value is 

activated 

2) Actuator is configured to 

work with process 

controller 

1) Check set‐value 

parameters ‐> see 

instrucions AMS‐PSCS 

2) Connect process sensor 

  

  

  

  

  

   Actuator position does not 

correspond to set‐value input 

A non‐linear valve curve has 

been parameterised 

Verify parameterised 

characteristic ‐> see 

instructions AMS‐PSCS 

  

  

  

  

  

  

  

   Operating conditions 

Probable reasons 

Possible remedy 

  

  

  

  

  

   Normal operating condition 

  

  

  

  

  

  

 

  

   Actuator in commissioning mode 

  

Commissioning mode will be 

left automatically after 

completion 

  

  

  

  

  

   Actuator not commissioned 

  

Depending on the type of 

cut‐offs, the actuator has to 

be commissioned either 

automatically or manually 

  

  

  

  

  

  

  

   Faults within the actuator’s 

environment 

Probable reasons 

Possible remedy 

  

  

  

  

  

   Too high torque has been 

encountered within the valve stroke 

1) Actuator not correctly 

commissioned to the valve 

2) Mechanical block within 

the stroke path 

3) Improper selection of the 

actuator  

1) Repeat commissioning 

2) Check valve and actuator 

for unobstructed running 

3) Check actuator selection 

  

  

  

  

 

  

   1) No proper process feedback (only 

in combination with PSIC) 

2+3) Maximum control range 

exceeds (only in combination with 

PSIC) 

1) Process feedback wrongly 

or not at all connected  

2) Process feedback outside 

od adjusted range 

3) No process sensor signal 

available 

1) Apply the correct process 

feedback signal and check 

polarity  

2) Ensure the correct process 

feedback range 

3) Check the process sensor 

and its supply voltage 

Summary of Contents for ILEA-Ax

Page 1: ...ctuators ILEA Ax ILEA Bx ILEA Px ILEA Qx ILEA_IOM ILEA_IOM_RevDc_0721 92500136 RevC TABLE OF CONTENTS Designations 2 Symbols and Safety 2 Actuator Mounting 3 General Safety 4 Wiring Commissioning 5 Sy...

Page 2: ...nel involved in the installation start up operation maintenance and repair of the actuators Beware of mechanical hazards due to electrically powered actuator components With the actuator powered elect...

Page 3: ...3 35 1 18N 3 91 1 28E 28M 3 46 2 29E 3 46 2 29S 3 03 1 58E 3 46 2 58T 3 35 1 NS PICV Pxx 2 67 2 GENERAL SAFETY ILEA actuators are built with state of the art technology and are safe to operate with c...

Page 4: ...f the actuator is removed from the control valve upon reinstallation the auto calibration procedure must be performed CONTROL SIGNAL AND POSITION FEEDBACK CHOICES AND LABEL DESIGNATIONS SIGNAL 2 WAY V...

Page 5: ...ocess Sensor Option Position switch potential free contact Electric supply for 1 phase AC DC COMMISSIONING CAUTION ELECTRICAL OPERATION OF THE ACTUATOR IS ALLOWED ONLY AFTER MOUNTING TO A VALVE AUTOMA...

Page 6: ...see instrucions AMS PSCS 2 Connect process sensor x x Actuator position does not correspond to set value input A non linear valve curve has been parameterised Verify parameterised characteristic see i...

Page 7: ...passed over Valve seat worn or defective Check the valve seat x x Actuator supply voltage too low 1 Improper wiring of the mains supply 2 Jitter in supply voltage 3 Too low supply voltage from PSEP wi...

Page 8: ...2600 EMRICK BLVD BETHLEHEM PA 18020 USA 800 922 0085 WWW WARRENCONTROLS COM DEPENDABLE RUGGED PRECISION CONTROL VALVES AND ACCESSORIES ILEA_IOM_RevDc_0721 92500136 RevC...

Reviews: