background image

2

2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com

SYMBOLS AND SAFETY

Pillar

Clamping Screws 

for Spring Pack

Valve Stem
Locking Nut

Yoke Lock Nut

Coupling

Coupling Nut

Bracket

Pillar Nut

ACTUATOR PART DESIGNATIONS

Please ensure that the detailed operating instructions and the chapter on “Safety” in particular have been read and 

understood by all personnel involved in the installation, start-up, operation, maintenance and repair of the actuators.

Beware of mechanical hazards due to electrically powered actuator components! With the actuator powered 

electrically, operating the unit holds the danger of crushing your finger!

Caution! During the installation of the actuator on the valve, the unit must not be powered electrically. Disconnect 

voltage from the actuator before maintenance and adjustment work. 

During adjustment work, the actuator must be operated by means of the handwheel only. Do not operate electrically!

DO NOT FULLY EXTEND. 

Summary of Contents for ILEA-Ax

Page 1: ...ctuators ILEA Ax ILEA Bx ILEA Px ILEA Qx ILEA_IOM ILEA_IOM_RevDc_0721 92500136 RevC TABLE OF CONTENTS Designations 2 Symbols and Safety 2 Actuator Mounting 3 General Safety 4 Wiring Commissioning 5 Sy...

Page 2: ...nel involved in the installation start up operation maintenance and repair of the actuators Beware of mechanical hazards due to electrically powered actuator components With the actuator powered elect...

Page 3: ...3 35 1 18N 3 91 1 28E 28M 3 46 2 29E 3 46 2 29S 3 03 1 58E 3 46 2 58T 3 35 1 NS PICV Pxx 2 67 2 GENERAL SAFETY ILEA actuators are built with state of the art technology and are safe to operate with c...

Page 4: ...f the actuator is removed from the control valve upon reinstallation the auto calibration procedure must be performed CONTROL SIGNAL AND POSITION FEEDBACK CHOICES AND LABEL DESIGNATIONS SIGNAL 2 WAY V...

Page 5: ...ocess Sensor Option Position switch potential free contact Electric supply for 1 phase AC DC COMMISSIONING CAUTION ELECTRICAL OPERATION OF THE ACTUATOR IS ALLOWED ONLY AFTER MOUNTING TO A VALVE AUTOMA...

Page 6: ...see instrucions AMS PSCS 2 Connect process sensor x x Actuator position does not correspond to set value input A non linear valve curve has been parameterised Verify parameterised characteristic see i...

Page 7: ...passed over Valve seat worn or defective Check the valve seat x x Actuator supply voltage too low 1 Improper wiring of the mains supply 2 Jitter in supply voltage 3 Too low supply voltage from PSEP wi...