background image

4

2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com

SET UP & GENERAL SAFETY

With power applied, preferably, use a signal calibrator to 
verify that the valve is fully stroking from one end to the 
other as depicted by the travel indicator on the side of 
the actuator mounting Pillar and with the proper control 
action. Alternately the process controller could be directly 
connected to test if it has a ‘Manual-Mode’ of operation 
where the controllers output can be manually adjusted from 
0% - 100%.

IF THE ACTUATOR IS ONE WITH A DEFINED ‘FAIL-SAFE’ 
DIRECTION ,THAT CAN BE VERIFIED BY:

1. Using the signal calibrator to move the 

actuator position to mid-stroke.

2. Safely disconnecting power at the power 

breaker switch and observing the actuator 
going to its fail-safe position.

Once these steps are verified you may proceed to 
commissioning the control valve. If either of these tests did 
not perform as expected, then contact the Warren Controls 
factory for further troubleshooting steps.

BASIC SAFETY NOTES:
• Before opening the actuator cover, ensure that the electrical 
mains supply voltage is disconnected.

• If operating the actuator with the cover removed for 
troubleshooting reasons make sure the wiring terminations 
are clearly understood. Contract the Warren Controls factory 
for further troubleshooting steps as may be necessary.

• Do NOT attempt to auto-stroke the actuator when the 
actuator is not connected to a control valve as it will not 
function.

• Do NOT adjust the Manual Override completely downward 
when the actuator is not connected to a control valve as this 
could permanently damage the actuator.

•If the actuator is removed from the control valve, upon 
reinstallation the auto-calibration procedure must be 
performed.

CONTROL SIGNAL AND POSITION FEEDBACK CHOICES AND LABEL DESIGNATIONS.

SIGNAL

2-WAY VALVE CLOSED

LABEL 

DESIGNATION

3-WAY VALVE 

LOWER PORT CLOSED

LABEL

DESIGNATION

4 – 20 mA

@ 4 mA

20 – 4 mA CL

@ 4 mA

20 – 4 mA DN

4 – 20 mA

@ 20 mA

4 – 20 mA CL

@ 20 mA

4 – 20 mA DN

0 – 20 mA

@ 0 mA

20 – 0 mA CL

@ 0 mA

20 – 0 mA DN

0 – 20 mA

@ 20 mA

0 – 20 mA CL

@ 20 mA

0 – 20 mA DN

2 – 10 Vdc

@ 2 Vdc

10 – 2 Vdc CL

@ 2 Vdc

10 – 2 Vdc DN

2 – 10 Vdc

@ 10 Vdc

2 – 10 Vdc CL

@ 10 Vdc

2 – 10 Vdc DN

0 – 10 Vdc

@ 0 Vdc

10 – 0 Vdc CL

@ 0 Vdc

10 – 0 Vdc DN

0 – 10 Vdc

@ 10 Vdc

0 – 10 Vdc CL

@ 10 Vdc

0 – 10 Vdc DN

‘Signal’ as 20-4 CL, to indicate it is a 4 – 20 mA signal and CLOSED at 4 ma. The actuator should be preprogrammed for control 
action and which signal is designated. Switching from a milliamp signal to a voltage signal is simply a matter of wiring termination. 
Switching whether the control signal is ZERO based or not, or the control action must be done in the software set up. This can 
be done on the job site as necessary with the programming umbilical cord option along with a laptop computer that has a USB 
connection. If this is required, contact the Warren Controls factory.

Electric installation as well as over-current and over-voltage protection devices must be conform to the standard 

DIN IEC 60364-4-41, protection class I resp. protection class III (24VAC/24VDC)  and also to the standard DIN IEC 

60364-4-44 according to the applied over-voltage category of the actuator.

Please protect all of the power supply and control cables in front of the terminals mechanically by 

using suitable measures against unintentional loosening. 

Remove 

connection 

terminal cover

Never install the power supply and the control cables 

together in one conduit but instead please always use 

two different conduit.

Summary of Contents for ILEA-Ax

Page 1: ...ctuators ILEA Ax ILEA Bx ILEA Px ILEA Qx ILEA_IOM ILEA_IOM_RevDc_0721 92500136 RevC TABLE OF CONTENTS Designations 2 Symbols and Safety 2 Actuator Mounting 3 General Safety 4 Wiring Commissioning 5 Sy...

Page 2: ...nel involved in the installation start up operation maintenance and repair of the actuators Beware of mechanical hazards due to electrically powered actuator components With the actuator powered elect...

Page 3: ...3 35 1 18N 3 91 1 28E 28M 3 46 2 29E 3 46 2 29S 3 03 1 58E 3 46 2 58T 3 35 1 NS PICV Pxx 2 67 2 GENERAL SAFETY ILEA actuators are built with state of the art technology and are safe to operate with c...

Page 4: ...f the actuator is removed from the control valve upon reinstallation the auto calibration procedure must be performed CONTROL SIGNAL AND POSITION FEEDBACK CHOICES AND LABEL DESIGNATIONS SIGNAL 2 WAY V...

Page 5: ...ocess Sensor Option Position switch potential free contact Electric supply for 1 phase AC DC COMMISSIONING CAUTION ELECTRICAL OPERATION OF THE ACTUATOR IS ALLOWED ONLY AFTER MOUNTING TO A VALVE AUTOMA...

Page 6: ...see instrucions AMS PSCS 2 Connect process sensor x x Actuator position does not correspond to set value input A non linear valve curve has been parameterised Verify parameterised characteristic see i...

Page 7: ...passed over Valve seat worn or defective Check the valve seat x x Actuator supply voltage too low 1 Improper wiring of the mains supply 2 Jitter in supply voltage 3 Too low supply voltage from PSEP wi...

Page 8: ...2600 EMRICK BLVD BETHLEHEM PA 18020 USA 800 922 0085 WWW WARRENCONTROLS COM DEPENDABLE RUGGED PRECISION CONTROL VALVES AND ACCESSORIES ILEA_IOM_RevDc_0721 92500136 RevC...

Reviews: