5
ILEA_IOM_RevDc_0721
WIRING TERMINATION (A/B ONLY)
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
TTL
Button
+0(2) - 10
V
+ 0(4) - 20 mA
GND
+ 0(2) - 10
V
+ 0(4) - 20 mA
GND
max. Last/max. L
oad
100 mA/a
t 24
VD (
O
ption)
L/ + O
pen
N/-
L/ + C
lose
N/- (24V A
C/DC
) (
O
ption)
L/+ (24V A
C/DC
)
21-40
VDC/ 100 mA
+ 0(2) - 10
V
+ 0(4) - 20 mA
GND
(O
ption)
(O
ption)
(O
ption)
(O
ption)
L/+(see tag pla
te)
N/-(see tag pla
te)
PE
(O
ption)
24 V
AC/DC
(OPTION)
115V- 230V
AC
Control
Signal
Input
Position
Feedback
Output
M
onit
or r
ela
y
pot
en
tial-fr
ee
Binary
Input
signals
Fail
safe
signal
Supply
Actual
value
Closed
Open
Supply
Voltage
Fieldbus
In
ter
fac
e
PC
Communica
tion
Commissioning
Galvanically isolated 1 kV
Process-Sensor
(Option)
Position switch
potential-free
contact
Electric supply for 1-phase AC/DC
COMMISSIONING
CAUTION! ELECTRICAL OPERATION OF THE ACTUATOR IS ALLOWED ONLY AFTER
MOUNTING TO A VALVE!
AUTOMATIC COMMISSIONING
(Only available if at least one of the cut-offs is set to be “by force/torque” or
“by position automatically”.)
1
Press the commissioning button for 3 sec
2
Commissioning in progress
(Green LED is flashing, actuator
drives in both positions).
3
Green LED lights – Actuator successfully
commissioned and ready to be used.
OPERATING DISPLAY
– CONTROLS
ILEA actuators are commissioned at the factory when
mounted to a control Valve.
It must be commissioned if provided separately from a valve
or has been dismounted.
The actuator can only be commissioned when correctly
mounted to a valve and with at least one cut off set to “force/
torque.