- 27 -
Solenoid valve 30012
The solenoid valve
30012
(available as accessory) prevents the tank from emptying in case the fuel system fails. The
fuel filter should be installed before the solenoid valve.
Our recommendations in the following installation configurations:
Preferred installation layout (solenoid valve 30012 is not
required)
1. Fuel level is below the heater/stove. See figure 1.
• No special accessories required
Solenoid valve 30012 is recommended
2. Fuel level may temporarily rise above the heater/stove (e.g. in
the fuel tank filler pipe or when the boat tilts). See figure 2.
• No special accessories required but solenoid valve 30012 is
recommended.
Less desirable installation arrangement (solenoid valve
30012 must be installed)
3. Fuel level is above the heater/stove. See figure 3.
• Less desirable installation arrangement
• Possible siphon problem
• Solenoid valve
30012
must be installed in the fuel hose near the
tank.
If the fuel level in the tank is above the device, a solenoid valve 30012 must be installed in the fuel line
immediately after the tank lead-through.
Summary of Contents for Spartan
Page 1: ......
Page 11: ...9 Measures Viking water...
Page 17: ...15 Installation example 2 Water coolant installation example hot water tank calorifier...
Page 64: ...9 Viking water mitat...
Page 70: ...15 Esimerkkiasennus 2 Makeavesi l mm nsiirto j rjestelm n esimerkkiasennus l mminvesivaraaja...
Page 109: ......