765-4501/0100-0000
Properties
Product manual | Version: 1.1.0
21
8PORT IOL-A FLD EI DC 24V 2.0A
Property
Value
Output current, L1
Maximum: 4.0 A per channel per IEC 61131-2
Output current, L1 with IO-Link operating mode
Maximum 1.0 A with conductor size AWG 22/0.34 mm
2
and cable length of up to 20 m (per IO-Link specifica-
tion)
Maximum 4.0 A with increased conductor cross-sec-
tion or reduced cable length (max. voltage drop of
1.2 V for both feed and return line individually)
Output current, L2
Maximum: 4.0 A per channel per IEC 61131-2
Output current, L2 with IO-Link operating mode
Maximum 1.0 A with conductor size AWG 22/0.34 mm
2
and cable length of up to 20 m (per IO-Link specifica-
tion)
Maximum 4.0 A with increased conductor cross-sec-
tion or reduced cable length (max. voltage drop of
1.2 V for both feed and return line individually)
Circuit
High-side driver
The 1L+/2L+ output is not resistant to reverse power
feeding.
The input voltage must not exceed the supply voltage.
Self-protection
Overcurrent, overload, overtemperature and overvolt-
age
Voltage drop through high-side path
Less than 200 mV
Maximum capacitive load
1000 μF parallel to 24 Ω; 0.1 Hz
470 μF parallel to 12 Ω; 0.1 Hz
220 μF parallel to 6 Ω; 0.1 Hz
Maximum inductive load
1.15 H / 2 A; 0.2 Hz; DC13
Diagnostics (1L+)
Events: overcurrent, overload, overtemperature and
overvoltage