765-4501/0100-0000
Planning
Product manual | Version: 1.1.0
63
8PORT IOL-A FLD EI DC 24V 2.0A
Connection Example 2
Now we increase the current consumption on the two ports X01 and X02 of the
765-1701/0200-0000 IO-Link Hub to 2 A and check whether this is permissible:
The ports of the 765-1701/0200-0000 IO-Link Hub can withstand a constant load of 2 A.
However, the effects on the 765-4501/0100-0000 product must be considered.
Figure 6: Power Supply Group with 765-4501/0100-0000 – Connection Example 2
To do so, we consider port X01 of the 765-4501/0100-0000 module:
This has a load of 5.2 A = 2 A + 2 A + 0.5 A + 0.5 A + 0.2 A on pin 1. This exceeds the
maximum load capacity of 4 A and it thus not permitted.
If the currents on X01 and X02 of the 765-1701/0200-0000 IO-Link Hub were increased,
the overload protection would constantly activate and could threaten destruction of the
765-4102/0100-0000 IO-Link Master on its port X01.
6.3 Settings Options
6.3.1 Module Parameters
The “Exclusive Owner” connections 1, 5 and 9 and the “Input Only” connections 4, 8 and
12 require the following parameters and settings. The scanner transfers these parame-
ters to the product when the connection is established.
Parameters 10 to 85
Parameters 10 to 15 configure IO-Link port X01.
Parameters 20 to 25 configure IO-Link port X02.
...
Parameters 80 to 85 configure IO-Link port.
Table 46: IO-Link Master Parameters
No.
Parametername
Value Range
Default
Description
10, 20, ... IO-Link port X01/
X02/... – Port mode
0 ... 4
2
Port operating mode (configuration of pin 4)
0: Deactivated
Pin 4 is deactivated.
1: IOL Manual
Pin 4 is operated as an IO-Link port with
manual configuration.
2: IOL Autostart
Pin 4 is operated as an IO-Link port with
automatic configuration (plug and play).