765-4501/0100-0000
Commissioning
90
Product manual | Version: 1.1.0
8PORT IOL-A FLD EI DC 24V 2.0A
10.3.1.3.6 Revision ID
This shows the version ID of the connected device.
A value of 0 means: no device connected.
All other values must be interpreted as the version ID of the connected device.
10.3.1.3.7 Baud Rate
If an IO-Link device is connected to the port, its data transmission rate appears here. For
IO-Link, the transmission rate of the communication between the port and a connected
device can have the following values:
• 4.8 kbit/s (COM1)
• 38.4 kbit/s (COM2)
• 230.4 kbit/s (COM3)
If no IO-Link device is connected to the port, the text
Not connected
appears here.
10.3.1.3.8 Cycle Time
The cycle time of the master is bit-coded as follows:
• Bits 0 ... 5 specify a whole-number multiplier between 0 and 63.
• Bits 6 ... 7 specify the calculation formula to use according to the following table:
Table 57: Cycle Time of the Master – Bits 6 ... 7
Bits 6 ... 7
Calculation Formula
0
Multiplier × 0.1 ms
1
6.4 ms + multiplier × 0.4 ms
2
32.0 ms + multiplier × 1.6 ms
3
Reserved
10.3.1.3.9 Input Data Length
This shows the actual input data length of the connected product in bytes.
10.3.1.3.10 Vendor ID
This value is the manufacturer ID of the connected product.
10.3.1.3.11 Device ID
This value is the device ID of the connected product.
10.3.1.3.12 Displaying Process Data
You can view the process data associated with a specific port on the
Process Data
tab.
Proceed as follows to view the process data for a port:
1. From the main menu of the Webserver (left), select the menu item which you want to
view information about.
2. Open the
Process Data
tab.